Plan Review Notes
Plan Review Notes For Permit 15100361
Permit Number 15100361
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-10-14 11:37:14FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.