Notes |
Date |
Text |
2015-10-14 11:37:14 | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | UPWARD MOVEMENT. |
|