2015-10-14 14:48:45 | 1ST REVIEW: FBC 2010 MECHANICAL | | REVISION #15100349 | | MASTER #15020941 | | | | 1) THE NEW RETURN GRILLS AND 18 " TRANSFER DUCT IN THE | | OPEN AREA SEEM TO BE LOCATED IN THE WRONG LOCATION. | | PROVIDE A DUCTED RETURN FROM THE WORSHIP ROOM BACK TO | | THE RELOCATED AHU FOR BALANCED RETURN AIR- SECTION | | 601.2 FBC-10 MECHANICAL, | | 2) CLARIFY IF A DUCT SMOKE DETECTOR IS BEING RELOCATED | | WITH THE AHU AND PROVIDE DETAILS. | | 3) SHOW THE REQUIRED CLEARANCE SPACE DIMENSIONS AROUND | | THE AIR HANDLER IN THE CLOSET- REFER TO SECTION | | 603.1.3. | | 4) INDICATE THE TYPE AND SIZE OF DOOR FOR THE AHU | | CLOSET- SEE SECTIONS 306.1 AND 603.1. | | 5) PROVIDE A REVISED ELECTRICAL PLAN SHOWING THE NEW | | CIRCUITRY FOR THE RELOCATED AIR HANDLER . | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|