2015-10-14 14:48:451ST REVIEW: FBC 2010 MECHANICAL
 REVISION #15100349
 MASTER #15020941
  
 1) THE NEW RETURN GRILLS AND 18 " TRANSFER DUCT IN THE
 OPEN AREA SEEM TO BE LOCATED IN THE WRONG LOCATION.
 PROVIDE A DUCTED RETURN FROM THE WORSHIP ROOM BACK TO
 THE RELOCATED AHU FOR BALANCED RETURN AIR- SECTION
 601.2 FBC-10 MECHANICAL,
 2) CLARIFY IF A DUCT SMOKE DETECTOR IS BEING RELOCATED
 WITH THE AHU AND PROVIDE DETAILS.
 3) SHOW THE REQUIRED CLEARANCE SPACE DIMENSIONS AROUND
 THE AIR HANDLER IN THE CLOSET- REFER TO SECTION
 603.1.3.
 4) INDICATE THE TYPE AND SIZE OF DOOR FOR THE AHU
 CLOSET- SEE SECTIONS 306.1 AND 603.1.
 5) PROVIDE A REVISED ELECTRICAL PLAN SHOWING THE NEW
 CIRCUITRY FOR THE RELOCATED AIR HANDLER .
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER