2015-10-29 12:21:02 | BUILDING PLAN REVIEW |
| REVISION: 15100336 |
| PERMIT: 14120130 |
| ADD: 1901 S. DIXIE HWY. |
| CONT: SISCACONSTRUCTION |
| TEL: (561)686-5545 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1) THE LISTED PROVISO REQUIRES THE PRODUCT APPROVAL TO |
| BE SUBMITTED. WHEN SUBMITTING THE PRODUCT APPROVAL |
| CIRCLE THE TYPE OF GLAZYING INSTALLED, SIZE OF GLAZING |
| AND ASSOCIATED PRESSURES, MULLIONS, SPANS AND |
| PRESSURES, TYPES OF FASTENERS AND CORESSPONDING |
| FASTENERS. |
| NOTE, THE PRODUCT APPROVAL IS ONLY FOR THE STOREFRONT |
| WINDOW SYSTEM, NOT THE DOOR FRAME. |
| |
| 107.3.4.1. THOSE PRODUCTS WHICH ARE REGULATED BYDCA |
| RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| |
| 2ND REVIEW |
| DATE: THURS. OCT. 29/ 2015 |
| ACTION: DENIED |
| |
| 2ND REQUEST. THE PRODUCT APPROVALS ARE TO BE REVIEWED |
| BY THE DESIGNER OF RECORD. NOTE THE DESIGNER OF RECORD |
| STAMPED APPROVED ON THE SHOP DRAWINGS FOR YKK YHS 50FS |
| FL # 14218.2. |
| |
| THE FLORIDA APPROVAL FL # 14218-R4 HAS THE SUB-SYSTEM |
| 14218.2 YHS 50 FI HIGHLIGHTED THIS IS A DIFFERENT |
| SUB-SYSTEM THAN SUBMITTED AND APPROVED THROUGH THE SHOP |
| DRAWINGS. THE DESIGNER OF RECORD HAS NOT STAMPED |
| REVIEWED. |
| |
| THE FLORIDA APPROVAL FL # 15916-R1 HAS NOT BEEN |
| REVIEWED BY THE DESIGNER OF RECORD, NOR STAMPED |
| APPROVED. |
| |
| A MIAMI-DADE NOA 14-0708.07 BILCO ROOF HATCH SUBMITTED |
| NOT REVIEWED OR APPROVED BY THE DESIGNER OF RECORD. |
| |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 107.3.4.1 THOSE |
| PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| |