2015-10-16 14:30:39 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | | | 1. A BACKFLOW PREVENTER IS REQURED FOR COFFE MACHINE | | AND ICE MACKER. PER FBC P SEC 608.16.10 COFFEE MACHINES | | AND NONCARBONATED BEVERAGE DISPENSERS. | | THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND | | NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED | | AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO | | ASSE 1022 OR BY AN AIR GAP. | | 2.P-1 SHOWS ICE MACHINEIN LUNCH PREP ROOM WITH NO | | PLUMBING FEEDING IT IS IT EXISTING PLEASE CLARIFY. PER | | WPB AMEND. TO FBC SEC 107.2.1 |
|