2015-11-17 15:29:39 | FAILED |
| |
| 1) REPEAT COMMENT: ALL ELEVATIONS, SECTIONS, ROOF PLANS |
| AND DETAIL SHEETS SHALL BE REVISED TO ACCURATELY |
| REFLECT THE LOWER BUILDING HEIGHT TO MEET THE |
| REQUIREMENTS OF RESOLUTION NO. 49-13. THE BACK-UP |
| GRAPHIC INCLUDED WITH THE ORIGINAL PERMIT INDICATED |
| THAT THE SLOPED TOWER ROOF MET THE HEIGHT FOR ONE |
| SPECIFIC SECTION OF THE BUILDING; HOWEVER, UPON REVIEW |
| OF THE CURRENTLY SUBMITTED SHEETS IT APPEARS THAT THE |
| BUILDING EXCEEDS THE HEIGHT EXCEPTION AT SOME OF THE |
| AREAS HOUSING THE MECHANICAL EQUIPMENT AND STAIR |
| ENCLOSURES AS WELL AS THE PARAPETS. THE ELEVATION |
| DIMENSION SHALL BE SHOWN FROM THE AVERAGE ELEVATION OF |
| THE FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT |
| OF THE AREAS UTILIZING THE HEIGHT EXCEPTION. THIS HAS |
| NOT BEEN PROVIDED ON THE ELEVATION, SECTION AND |
| STRUCTURAL SHEETS LISTED BELOW (NOTE: ALL SHEETS SHALL |
| BE VERIFIED FOR CORRECT HEIGHT DIMENSIONS REGARDLESS OF |
| LISTING BY STAFF BELOW. FAILURE TO UPDATE A SHEET THAT |
| IS NOT LISTED WILL RESULT IN THE PERMIT NOT PASSING). |
| |
| A. PHASE ONE ELEVATIONS |
| |
| SHEET A201A |
| SHEET A201B |
| SHEET A202 |
| SHEET A203 |
| SHEET A204 |
| SHEET A205 |
| SHEET A206 |
| SHEET A207 |
| SHEET A301 - THE REVISED SHEET DOES NOT SHOW THE |
| CORRECT DIMENSION POINTS AND THE BUILDING APPEARS TOO |
| TALL. |
| SHEET A352 - THE REVISED SHEET DOES NOT SHOW THE |
| CORRECT DIMENSION POINTS AND THE BUILDING APPEARS TOO |
| TALL. |
| |
| B. PHASE ONE SECTION DRAWINGS |
| |
| SHEET A302 |
| SHEET A303 |
| SHEET A304 |
| SHEET A491 |
| SHEET A492 |
| SHEET A496 |
| SHEET A497 |
| |
| C. PHASE TWO ELEVATIONS |
| |
| SHEET A201A |
| SHEET A201B |
| SHEET A204 |
| |
| D. PHASE TWO SECTIONS |
| |
| SHEET A302 |
| SHEET A304 |
| SHEET A315 |
| SHEET A352 |
| SHEET A493 |
| SHEET A498 |
| |
| E. STRUCTURAL SHEETS FOR BOTH PHASES SHALL BE UPDATED |
| TO SHOW THE FULL HEIGHT DIMENSION FROM GRADE. |
| |
| F. A NEW SHEET A315 WAS PROVIDED IN ORDER TO SHOW THAT |
| THE BUILDING DOES NOT EXCEED THE PERMITTED HEIGHT. |
| HOWEVER, THE SHEET A315 IS A DETAIL SHEET REFERENCED ON |
| SHEET A303, WHICH WAS NOT REVISED. THE NEW DETAILS ON |
| SHEET A315 DO NOT MATCH THE DETAILS SHOWN ON SHEET A303 |
| FOR THE TOP OF THE PARAPET. ADDITIONALLY, THE |
| DIMENSIONS SHOWN PREVIOUSLY ON SHEET A303 SHOW A |
| BUILDING WHICH EXCEEDS THE PERMITTED HEIGHT. |
| |
| G. THE HEIGHT DIMENSIONS ON SHEET A353 WERE NOT |
| PROVIDED FROM GRADE ON THE OVERALL SECTION DRAWING. |
| NOTE: IF THE FIVE (5) INCHES ABOVE AVERAGE GRADE SHOWN |
| ON THE CUT SHEET PROVIDED WITH THE ORIGINAL PERMIT ARE |
| ADDED TO THE BUILDING HEIGHT, THEN THE BUILDING EXCEEDS |
| THE PERMITTED HEIGHT EXCEPTION. |
| |
| H. STAFF IS UNABLE TO LOCATE WHERE THE PARAPET RAILING |
| DETAIL CALLED OUT ON SHEET A353(8) IS ON THE ELEVATIONS |
| OR FULL SECTION DRAWINGS. NO OVERALL HEIGHT DIMENSION |
| IS GIVEN TO THE TOP OF THE RAIL. |
| |
| 2) PRIOR TO C.O. THE MINOR PD AMENDMENT TO REFLECT THE |
| CHANGES TO THE BICYCLE RACK LOCATION AND THE WALKWAY |
| ORIENTATION SHALL BE SUBMITTED TO AND APPROVED BY THE |
| PLANNING DIVISION. |
| |
| 3) SHEET C101 SHOWS NOTE REFERENCING AN 18 FOOT CLEAR |
| FIRE TRUCK ACCESS ROAD (SOUTH OF POOL WALL). THE |
| APPROVED SITE PLAN SHOWS THIS AS A 20 FOOT WIDE |
| DRIVEWAY. ALL PLANS SHALL SHOW THE APPROVED 20 FOOT |
| DRIVE CONDITION. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
| |
| |
| |
| |
| |