Plan Review Notes
Plan Review Notes For Permit 15100321
Permit Number 15100321
Review Stop P
Sequence Number 1
Notes
Date Text
2015-10-31 05:11:551) SHT.063-AS109 - ELEVATION DETAIL #3 IS MISLEADING
 AND THE HEIGHT OF THE COUNTER FOR THE SINK IS UNCLEAR
 AS DIMENSIONED ON THE RIGHT SIDE OF THE DETAIL.IT IS
 DIFFICULT TO DETERMINE THE HEIGHT TO THE TOP OF THE
 COUNTER. CLARIFY.
 2) SHT. 146-A400 - THE MINIMUM HEIGHT DIMENSIONS TO THE
 TOP OF THE BACKING FOR THE GRAB BARS DOES NOT COMPLY
 WITH THE FAIR HOUSING ACT. THE MINIMUM HEIGHT TO THE
 TOP OF THE BACKING FOR THE WATER CLOSET SHALL BE 38
 INCHES, NOT 36 INCHES AS SHOWN.
 B) THE MINIMUM HEIGHT DIMENSION TO THE TOP OF THE
 BACKING FOR THE GRAB BARS ON THE CONTROL WALL FOR THE
 TUB AND SHOWER SHALL BE LOCATED AT 38 INCHES, NOT 36
 INCHES AS SHOWN.
 C) THE BOTTOM OF THE BACKING FOR THE GRAB BAR ON THE
 BACK WALL OF THE TUB SHALL BE LOCATED A AMXIMUM OF 6
 INCHES ABOVE THE LIP ( TOP) OF THE TUB.
 3) THE RESPONSE TO COMMENT #8 REFERS TO DRAWING #
 A103B. THERE IS NO SUCH DRAWING IN THIS SUBMITTAL.
 CLARIFY.
 4) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER.WPB
 AMEND. TO FBC SEC. 107.3.5.1.5.
 5) PLEASE SUBMIT THE CALCULATIONS THAT WERE DONE TO
 DETERMINE THE AMOUNT OF COMBUSTION AIR REQUIRED FOR THE
 GAS APPLIANCES AND HOW THAT COMBUSTION AIR IS BEING
 SUPPLIED TO THE AREAS. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.5.
 6) THE GAS SIZING TABLE REFERENCED ON SHT.297- P412 FOR
 THE 2 PSI SYSTEM FROM NFPA 54 APPEARS TO BE INCORRECT.
 PLEASE REFER TO TABLE 6.2 (C). I BELIEVE THIS IS THE
 CORRECT TABLE. CLARIFY.
 7) THE GAS SIZING TABLE REFERENCED ON SHT.297-P412 FOR
 THE 0.5 PSI SYSTEM FROM NFPA 54 APPEARS TO BE
 INCORRECT. PLEASE REFER TO TABLE 6.2 ( B ). I BELIEVE
 THIS IS THE CORRECT TABLE. CLARIFY.
 8) SHT. 297-P412 - SHOW THE PIPE SIZE DOWNSTREAM OF THE
 PRV AT LOCATION "G" ON THE GAS DRAWING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  