2015-10-31 05:11:55 | 1) SHT.063-AS109 - ELEVATION DETAIL #3 IS MISLEADING |
| AND THE HEIGHT OF THE COUNTER FOR THE SINK IS UNCLEAR |
| AS DIMENSIONED ON THE RIGHT SIDE OF THE DETAIL.IT IS |
| DIFFICULT TO DETERMINE THE HEIGHT TO THE TOP OF THE |
| COUNTER. CLARIFY. |
| 2) SHT. 146-A400 - THE MINIMUM HEIGHT DIMENSIONS TO THE |
| TOP OF THE BACKING FOR THE GRAB BARS DOES NOT COMPLY |
| WITH THE FAIR HOUSING ACT. THE MINIMUM HEIGHT TO THE |
| TOP OF THE BACKING FOR THE WATER CLOSET SHALL BE 38 |
| INCHES, NOT 36 INCHES AS SHOWN. |
| B) THE MINIMUM HEIGHT DIMENSION TO THE TOP OF THE |
| BACKING FOR THE GRAB BARS ON THE CONTROL WALL FOR THE |
| TUB AND SHOWER SHALL BE LOCATED AT 38 INCHES, NOT 36 |
| INCHES AS SHOWN. |
| C) THE BOTTOM OF THE BACKING FOR THE GRAB BAR ON THE |
| BACK WALL OF THE TUB SHALL BE LOCATED A AMXIMUM OF 6 |
| INCHES ABOVE THE LIP ( TOP) OF THE TUB. |
| 3) THE RESPONSE TO COMMENT #8 REFERS TO DRAWING # |
| A103B. THERE IS NO SUCH DRAWING IN THIS SUBMITTAL. |
| CLARIFY. |
| 4) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER.WPB |
| AMEND. TO FBC SEC. 107.3.5.1.5. |
| 5) PLEASE SUBMIT THE CALCULATIONS THAT WERE DONE TO |
| DETERMINE THE AMOUNT OF COMBUSTION AIR REQUIRED FOR THE |
| GAS APPLIANCES AND HOW THAT COMBUSTION AIR IS BEING |
| SUPPLIED TO THE AREAS. WPB AMEND. TO FBC SEC. 107.2.1, |
| 107.3.5.1.5. |
| 6) THE GAS SIZING TABLE REFERENCED ON SHT.297- P412 FOR |
| THE 2 PSI SYSTEM FROM NFPA 54 APPEARS TO BE INCORRECT. |
| PLEASE REFER TO TABLE 6.2 (C). I BELIEVE THIS IS THE |
| CORRECT TABLE. CLARIFY. |
| 7) THE GAS SIZING TABLE REFERENCED ON SHT.297-P412 FOR |
| THE 0.5 PSI SYSTEM FROM NFPA 54 APPEARS TO BE |
| INCORRECT. PLEASE REFER TO TABLE 6.2 ( B ). I BELIEVE |
| THIS IS THE CORRECT TABLE. CLARIFY. |
| 8) SHT. 297-P412 - SHOW THE PIPE SIZE DOWNSTREAM OF THE |
| PRV AT LOCATION "G" ON THE GAS DRAWING. |
| |