Plan Review Notes
Plan Review Notes For Permit 15100321
Permit Number 15100321
Review Stop G
Sequence Number 1
Notes
Date Text
2015-10-31 05:30:531) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER.WPB
 AMEND. TO FBC SEC. 107.3.5.1.5.
 2) PLEASE SUBMIT THE CALCULATIONS THAT WERE DONE TO
 DETERMINE THE AMOUNT OF COMBUSTION AIR REQUIRED FOR THE
 GAS APPLIANCES AND HOW THAT COMBUSTION AIR IS BEING
 SUPPLIED TO THE AREAS. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.5, FBC-FUEL GAS SEC. 304.5.
 3) THE GAS SIZING TABLE REFERENCED ON SHT.297- P412 FOR
 THE 2 PSI SYSTEM FROM NFPA 54 APPEARS TO BE INCORRECT.
 PLEASE REFER TO TABLE 6.2 (C). I BELIEVE THIS IS THE
 CORRECT TABLE. CLARIFY.
 4) THE GAS SIZING TABLE REFERENCED ON SHT.297-P412 FOR
 THE 0.5 PSI SYSTEM FROM NFPA 54 APPEARS TO BE
 INCORRECT. PLEASE REFER TO TABLE 6.2 ( B ). I BELIEVE
 THIS IS THE CORRECT TABLE. CLARIFY.
 5) SHT. 297-P412 - SHOW THE PIPE SIZE DOWNSTREAM OF THE
 PRV AT LOCATION "G" ON THE GAS DRAWING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  