2015-10-31 05:30:53 | 1) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER.WPB | | AMEND. TO FBC SEC. 107.3.5.1.5. | | 2) PLEASE SUBMIT THE CALCULATIONS THAT WERE DONE TO | | DETERMINE THE AMOUNT OF COMBUSTION AIR REQUIRED FOR THE | | GAS APPLIANCES AND HOW THAT COMBUSTION AIR IS BEING | | SUPPLIED TO THE AREAS. WPB AMEND. TO FBC SEC. 107.2.1, | | 107.3.5.1.5, FBC-FUEL GAS SEC. 304.5. | | 3) THE GAS SIZING TABLE REFERENCED ON SHT.297- P412 FOR | | THE 2 PSI SYSTEM FROM NFPA 54 APPEARS TO BE INCORRECT. | | PLEASE REFER TO TABLE 6.2 (C). I BELIEVE THIS IS THE | | CORRECT TABLE. CLARIFY. | | 4) THE GAS SIZING TABLE REFERENCED ON SHT.297-P412 FOR | | THE 0.5 PSI SYSTEM FROM NFPA 54 APPEARS TO BE | | INCORRECT. PLEASE REFER TO TABLE 6.2 ( B ). I BELIEVE | | THIS IS THE CORRECT TABLE. CLARIFY. | | 5) SHT. 297-P412 - SHOW THE PIPE SIZE DOWNSTREAM OF THE | | PRV AT LOCATION "G" ON THE GAS DRAWING. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|