Plan Review Notes For Permit 15100297 |
Permit Number |
15100297 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-22 06:57:04 | 1ST REVIEW: FBC 2010 MECHANICAL | | REVISION # 15100297 | | MASTER # 15010300 | | 10/22/15 | | | | 1) THE WPB DEVELOPMENT SERVICES BUILDING DIVISION | | REQUIRES SEPARATE PERMITS FOR KITCHEN HOODS AND FIRE | | SUPRESSION SYSTEMS. PLEASE REMOVE SHEET M7.1 & M7.2 | | FROM THE REVISED PLAN SETS OR PLACE NOTES ON THE PLAN | | TO CLARIFY THAT THE GREASE DUCT SHOWN IN THE TENANT | | SPACE IS FOR REFERENCE ONLY, AND WILL BE INSTALLED | | UNDER A SEPARATE PERMIT. | | 2) SHEET M2.2: PROVIDE ENGINEERED TIE-DOWN DETAILS FOR | | THE NEW CU 1-9 AND AC STAND- SECTION 301.12 FBC-10 | | MECHANICAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|