2015-10-22 06:57:041ST REVIEW: FBC 2010 MECHANICAL
 REVISION # 15100297
 MASTER # 15010300
 10/22/15
  
 1) THE WPB DEVELOPMENT SERVICES BUILDING DIVISION
 REQUIRES SEPARATE PERMITS FOR KITCHEN HOODS AND FIRE
 SUPRESSION SYSTEMS. PLEASE REMOVE SHEET M7.1 & M7.2
 FROM THE REVISED PLAN SETS OR PLACE NOTES ON THE PLAN
 TO CLARIFY THAT THE GREASE DUCT SHOWN IN THE TENANT
 SPACE IS FOR REFERENCE ONLY, AND WILL BE INSTALLED
 UNDER A SEPARATE PERMIT.
 2) SHEET M2.2: PROVIDE ENGINEERED TIE-DOWN DETAILS FOR
 THE NEW CU 1-9 AND AC STAND- SECTION 301.12 FBC-10
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER