2015-11-23 10:54:17 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6700 |
| [email protected] |
| ALTERNATE CONTACT |
| PHIL PETTY |
| 561-805-6742 |
| [email protected] |
| |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE |
| SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| FLOOR PLAN |
| FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| FEET OF EACH SLEEPING ROOM. |
| NEC 240.24 (A) & (B) PANELS SHALL BE LOCATED SUCH THAT |
| OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT OCCUPANTS |
| SHALL HAVE ACCESS TO OCP DEVICES. |
| NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. |
| FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| |
| |
| |