2015-11-19 13:14:30 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| CODE: FBC -5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- THE CURRENT CODE IS THE FBC-5TH EDITION (2014) NOT |
| 2010 FBC. REVISE ALL THE CODES REFERENCED. CHAPTER 553 |
| F. S. |
| |
| 3- THIS BUILDING IS LOCATED IN EXPOSURE "D" NO "C". |
| REVISE BUILDING EXPOSURE ON THE CODE ANALYSIS |
| INFORMATION AND REVISE ALL THE WINDOWS AND DOORS DESIGN |
| PRESSURES SHOWN ON EXTERIOR ELEVATIONS AND TABLES |
| SUBMITTED. SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 4- THIS IS NO ALTERATION LEVEL 2. THIS IS AND ADDITION. |
| REVISE CODE ANALYSIS INFORMATION AS REQUIRED. SEC. 507 |
| OF FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| |
| 5- THE CODE ANALYSIS INFORMATION IS NOT LEGIBLE. THERE |
| IS TOO MUCH BACKGROUND CONTRAST. PROVIDE CLEAR |
| INFORMATION. SEC. 107.2.1.4 CITY AMENDMENTS. |
| |
| 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. VALUATION WAS UPDATED TO $20,000. THE |
| PERMIT FEE BALANCE IS $548.28. |
| |
| 7- THE HOUSE DATA INFORMATION SHOWN BY THE FLOOR PLAN |
| IS INCORRECT. THE NEW FAMILY ROOM ADDITION IS 340 S.F. |
| NO 240S.F. (15'-0" X 22'-8" = 340). REVISE AS REQUIRED |
| AND COORDINATE THIS SQUARE FOOTAGE WITH VALUATION ON |
| ITEM #6 ABOVE. |
| |
| 8- ARCHITECT OF RECORD TO PROVIDE SPECIFICATIONS ON |
| PLAN SHOWING COMPLIANCE WITH THE HEATING REQUIREMENTS |
| OF SEC. R303.9 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 9- ROOF PLAN: CLARIFY SPACING OF THE 2X8 ROOF JOIST. |
| DRAWING SHOWS JOIST AT 16" O.C. , WHILE SPECIFICATIONS |
| ON THE SAME PLAN CALL FOR 2X8 JOIST AT 24" O.C. REVISE |
| AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 10- REVISE THE WALL SECTION: |
| A) NEED TO SPECIFY AT LEAST 8D RING SHANK NAILS AS |
| REQUIRED BY SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| B) CLARIFY ROOF SHEATHING FASTENING NOTE. CLARIFIED THE |
| NAILING SPACING. WHAT'S 7 4" O.C. IN ZONE 3?. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| C) SPECIFY ROOF PITCH SHOWING COMPLIANCE WITH SEC. |
| R905.11 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| D) NEED TO SHOW COMPLIANCE WITH THE 6" HEIGHT ABOVE |
| FINISHED GRADE AS REQUIRED BY SEC. R404.1.6 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| ALSO, NEED TO COMPLY WITH THE 12" BELOW FINISHED GRADE |
| AS REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). NOTE: MAKE SURE SIZE OF FOOTING |
| SPECIFIED WILL COMPLY WITH BOTH REQUIREMENTS. |
| |
| E) SHOW COMPLIANCE WITH THE 6" CLEARANCE FROM WALL |
| COVERING TO THE FINAL EARTH GRADE FOR TERMITE |
| INSPECTION AS REQUIRED BY SEC. R318.7 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). COORDINATE WITH |
| ITEM ABOVE. |
| |
| F) NEED TO PROVIDE CROSS VENTILATION AS REQUIRED BY |
| SEC. R806 OF FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE: |
| 4"X 24" SCREEN VENTS DON'T PROVIDE CROSS VENTILATION. |
| |
| G) CLEARLY SPECIFY CONNECTOR THAT FASTEN 2X6 STUDS TO |
| THE BOTTOM PLATE. SEC. R601.2 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| H) SPECIFY SPECIFY WALL INSULATION. COORDINATE WITH THE |
| ENERGY CALCULATIONS. SEC. R103.2 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| I) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 1/2" |
| BOTTOM PLATES ANCHORS. AND COORDINATE INFORMATION WITH |
| THE FRAMING DETAIL SHOWN ON THE TOP RIGHT OF SAME |
| DRAWING (INCLUDING ANCHOR SPACING). SEC. R601.2 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| J) NEED TO SPECIFY THE VAPOR RETARDER AS REQUIRED BY |
| SEC. R506.2.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| K) NEED TO SPECIFY 7/8" MIN. STUCCO THICKNESS AS |
| REQUIRED BY TABLE R702.1(1) OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| L) SPECIFICATIONS CALL FOR 2"X6" STUDS @16" O.C. WHERE |
| IS THE GABLE END WALL MENTIONED ON THE SAME |
| SPECIFICATION?. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 11- FRAMING DETAIL: CLEARLY SPECIFY ALL STRAPS (TYPE |
| AND SIZE). SEC. R601.2 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| 12- WINDOW MULLION NOA 11-1213.07 SUBMITTED: CLEARLY |
| IDENTIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| WITH THE REVISED DESIGN PRESSURES REQUIRED BY ITEM #3 |
| ABOVE. SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 13- FLAT ROOF NOA 14-0611.01 SUBMITTED: PROVIDE SIGNED |
| AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL |
| LIMITATION #7 OF SELECTED ASSEMBLY ON PAGE 27 AND THE |
| LAST PAGE OF NOA SUBMITTED. NEED THE RAS 117 |
| CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY |
| SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| |
| 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR THE SINGLE HUNG WINDOWS. NOA |
| 11-1115.08 SUBMITTED EXPIRED ON SEPTEMBER 22, 2015. |
| NEED TO PROVIDE CURRENT PRODUCT APPROVAL. |
| |
| 15- ARCHITECT OF RECORD TO APPROVE IN WRITING ALL THE |
| PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 16- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A) NEED TO PROVIDE CURRENT FORM. THE CURRENT BUILDING |
| CODE IN EFFECT IS THE 2014 CODE NOT 2010. FORM 402-2010 |
| SUBMITTED CAN NOT BE USED. CHAPTER 553 F.S. |
| |
| B) REVISE ITEM #5. THE TOTAL AREA IS 340 NOT 240. SEC. |
| R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| C) REVISE ITEM #6(B) TO MATCH TABLE 402A ON BACK OF |
| PAGE SUBMITTED. SEC. R101.5.1.1.1 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| D) ITEM #10 DOESN'T COMPLY WITH TABLE 402A ON BACK OF |
| PAGE SUBMITTED. NEED R-30 INSULATION. NOTE: R-30 |
| DOESN'T FIT ON 2X8 JOIST SPECIFIED ON PLANS. |
| PRESCRIPTIVE FORM 402 SUBMITTED DOESN'T COMPLY. NOTE: |
| PERFORMANCE FORM 405-2014 MAY BE USED INSTEAD TO COMPLY |
| WITH THE ENERGY CODE.. |
| |
| E) SPECIFY THE SEER/EER VALUE REQUIRED ON ITEM #12(B). |
| NOTE: PROVIDE MANUFACTURER SPECS SHOWING THE SEER VALUE |
| SPECIFIED ON THE INSTALLED VALUE ON TABLE 402A ON BACK |
| OF PAGE SUBMITTED . SEC. R103.2 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |