2015-11-19 13:14:30RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC -5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THE CURRENT CODE IS THE FBC-5TH EDITION (2014) NOT
 2010 FBC. REVISE ALL THE CODES REFERENCED. CHAPTER 553
 F. S.
  
 3- THIS BUILDING IS LOCATED IN EXPOSURE "D" NO "C".
 REVISE BUILDING EXPOSURE ON THE CODE ANALYSIS
 INFORMATION AND REVISE ALL THE WINDOWS AND DOORS DESIGN
 PRESSURES SHOWN ON EXTERIOR ELEVATIONS AND TABLES
 SUBMITTED. SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- THIS IS NO ALTERATION LEVEL 2. THIS IS AND ADDITION.
 REVISE CODE ANALYSIS INFORMATION AS REQUIRED. SEC. 507
 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 5- THE CODE ANALYSIS INFORMATION IS NOT LEGIBLE. THERE
 IS TOO MUCH BACKGROUND CONTRAST. PROVIDE CLEAR
 INFORMATION. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $20,000. THE
 PERMIT FEE BALANCE IS $548.28.
  
 7- THE HOUSE DATA INFORMATION SHOWN BY THE FLOOR PLAN
 IS INCORRECT. THE NEW FAMILY ROOM ADDITION IS 340 S.F.
 NO 240S.F. (15'-0" X 22'-8" = 340). REVISE AS REQUIRED
 AND COORDINATE THIS SQUARE FOOTAGE WITH VALUATION ON
 ITEM #6 ABOVE.
  
 8- ARCHITECT OF RECORD TO PROVIDE SPECIFICATIONS ON
 PLAN SHOWING COMPLIANCE WITH THE HEATING REQUIREMENTS
 OF SEC. R303.9 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 9- ROOF PLAN: CLARIFY SPACING OF THE 2X8 ROOF JOIST.
 DRAWING SHOWS JOIST AT 16" O.C. , WHILE SPECIFICATIONS
 ON THE SAME PLAN CALL FOR 2X8 JOIST AT 24" O.C. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 10- REVISE THE WALL SECTION:
 A) NEED TO SPECIFY AT LEAST 8D RING SHANK NAILS AS
 REQUIRED BY SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 B) CLARIFY ROOF SHEATHING FASTENING NOTE. CLARIFIED THE
 NAILING SPACING. WHAT'S 7 4" O.C. IN ZONE 3?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) SPECIFY ROOF PITCH SHOWING COMPLIANCE WITH SEC.
 R905.11 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) NEED TO SHOW COMPLIANCE WITH THE 6" HEIGHT ABOVE
 FINISHED GRADE AS REQUIRED BY SEC. R404.1.6 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 ALSO, NEED TO COMPLY WITH THE 12" BELOW FINISHED GRADE
 AS REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). NOTE: MAKE SURE SIZE OF FOOTING
 SPECIFIED WILL COMPLY WITH BOTH REQUIREMENTS.
  
 E) SHOW COMPLIANCE WITH THE 6" CLEARANCE FROM WALL
 COVERING TO THE FINAL EARTH GRADE FOR TERMITE
 INSPECTION AS REQUIRED BY SEC. R318.7 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). COORDINATE WITH
 ITEM ABOVE.
  
 F) NEED TO PROVIDE CROSS VENTILATION AS REQUIRED BY
 SEC. R806 OF FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE:
 4"X 24" SCREEN VENTS DON'T PROVIDE CROSS VENTILATION.
  
 G) CLEARLY SPECIFY CONNECTOR THAT FASTEN 2X6 STUDS TO
 THE BOTTOM PLATE. SEC. R601.2 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 H) SPECIFY SPECIFY WALL INSULATION. COORDINATE WITH THE
 ENERGY CALCULATIONS. SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 I) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 1/2"
 BOTTOM PLATES ANCHORS. AND COORDINATE INFORMATION WITH
 THE FRAMING DETAIL SHOWN ON THE TOP RIGHT OF SAME
 DRAWING (INCLUDING ANCHOR SPACING). SEC. R601.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 J) NEED TO SPECIFY THE VAPOR RETARDER AS REQUIRED BY
 SEC. R506.2.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 K) NEED TO SPECIFY 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 L) SPECIFICATIONS CALL FOR 2"X6" STUDS @16" O.C. WHERE
 IS THE GABLE END WALL MENTIONED ON THE SAME
 SPECIFICATION?. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- FRAMING DETAIL: CLEARLY SPECIFY ALL STRAPS (TYPE
 AND SIZE). SEC. R601.2 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 12- WINDOW MULLION NOA 11-1213.07 SUBMITTED: CLEARLY
 IDENTIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE REVISED DESIGN PRESSURES REQUIRED BY ITEM #3
 ABOVE. SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 13- FLAT ROOF NOA 14-0611.01 SUBMITTED: PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL
 LIMITATION #7 OF SELECTED ASSEMBLY ON PAGE 27 AND THE
 LAST PAGE OF NOA SUBMITTED. NEED THE RAS 117
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR THE SINGLE HUNG WINDOWS. NOA
 11-1115.08 SUBMITTED EXPIRED ON SEPTEMBER 22, 2015.
 NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
  
 15- ARCHITECT OF RECORD TO APPROVE IN WRITING ALL THE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 16- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) NEED TO PROVIDE CURRENT FORM. THE CURRENT BUILDING
 CODE IN EFFECT IS THE 2014 CODE NOT 2010. FORM 402-2010
 SUBMITTED CAN NOT BE USED. CHAPTER 553 F.S.
  
 B) REVISE ITEM #5. THE TOTAL AREA IS 340 NOT 240. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) REVISE ITEM #6(B) TO MATCH TABLE 402A ON BACK OF
 PAGE SUBMITTED. SEC. R101.5.1.1.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) ITEM #10 DOESN'T COMPLY WITH TABLE 402A ON BACK OF
 PAGE SUBMITTED. NEED R-30 INSULATION. NOTE: R-30
 DOESN'T FIT ON 2X8 JOIST SPECIFIED ON PLANS.
 PRESCRIPTIVE FORM 402 SUBMITTED DOESN'T COMPLY. NOTE:
 PERFORMANCE FORM 405-2014 MAY BE USED INSTEAD TO COMPLY
 WITH THE ENERGY CODE..
  
 E) SPECIFY THE SEER/EER VALUE REQUIRED ON ITEM #12(B).
 NOTE: PROVIDE MANUFACTURER SPECS SHOWING THE SEER VALUE
 SPECIFIED ON THE INSTALLED VALUE ON TABLE 402A ON BACK
 OF PAGE SUBMITTED . SEC. R103.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]