Plan Review Notes
Plan Review Notes For Permit 15100234
Permit Number 15100234
Review Stop B
Sequence Number 1
Notes
Date Text
2015-11-19 11:39:50CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE ENERGY CALCULATIONS.
  
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-103.2.1.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM 405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBCE-103.2.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 PROVIDE NOA FOR SWING GLASS DOORS.
 PROVIDE NOA FOR SINGLE HUNG WINDOWS.
 PROVIDE PRODUCT APPROVAL FOR GARAGE FLOOD VENTS.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS.
  
 PLEASE REVIEW NFIP COMMENTS.
  