2015-12-21 17:10:18 | 2ND REVIEW 2014 MECHANICAL |
| PERMIT #15100233 |
| 12/21/15 |
| |
| THE 1ST REVIEW COMMENTS STILL EXIST. I HAVE RE-PRINTED |
| THEM BELOW FOR REVIEW, PLEASE COMPLY. |
| 1) REFER TO SECTION C101.4.4 FBC-14 ENERGY |
| CONSERVATION: CHANGE IN OCCUPANCY OR USE. |
| SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD |
| RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL |
| OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE |
| THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE |
| C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1) |
| OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY |
| WITH SECTION C405.5. |
| IN ACCORDANCE WITH THIS SECTION PLEASE PROVIDE ENERGY |
| CALCULATIONS- SEE THE FOLLOWING SECTIONS FOR COMPLIANCE |
| SUBMITTAL INFORMATION: C101.5.1 COMPLIANCE MATERIALS. |
| THE FLORIDA BUILDING COMMISSION SHALL APPROVE SPECIFIC |
| COMPUTER SOFTWARE. THE CODE OFFICIAL SHALL BE PERMITTED |
| TO APPROVE WORKSHEETS, COMPLIANCE MANUALS AND OTHER |
| SIMILAR MATERIALS THAT MEET THE INTENT OF THIS CODE. |
| C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING |
| SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS |
| MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN |
| APPENDIX C. |
| 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING |
| CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS ON |
| THE PLAN IN ACCORDANCE WUITH TABLE 403.3 FBC-14 |
| MECHANICAL. THE CALCULATIONS SHALL INDICATE THE AMOUNT |
| OF CFM'S OF OUTSIDE AIR REQUIRED FOR THE RETAIL SPACE |
| OCCUPANTS, AND THE AMOUNT OF CFM'S PROVIDED BY THE |
| EXISTING OR PROPOSED SYSTEMS. |
| 3) MECHANICAL EXHAUST IS REQUIRED FOR THE NEW TOILET |
| ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL. |
| PLEASE REVISE THE PLANS TO SHOW COMPLIANCE. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |