Plan Review Notes
Plan Review Notes For Permit 15100233
Permit Number 15100233
Review Stop P
Sequence Number 1
Notes
Date Text
2015-10-13 06:59:191ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
  
 PLUMBING COMMENTS:
  
 1.SHOW CLEAR FLOOR SPACE FOR LAVATORY IN ACCESSIBLE
 BATHROOM.
 PER WPB AMEN. SEC 107.2.1
 2.GRAB BARS SHALL COMPLY WITH.FBC ACC SEC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
 3.TOILET SHALL COMPLY WITH FBC ACC.SEC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 4. A DRINKING FOUNTAIN IS REQUIRED TO COMPLY WITH FBC
 ACC. SEC
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 5.PROVIDE SANITARY AND WATER RISER DIAGRAM.
 PER WPB AMEN. 107 .3.5.1.3(13)
 THE FOLLOWING IS AN UPDATED PLUMBING REVIEW AS OF
 12/9/15;
 1) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK
 BEING DONE TO THE EXISTING TOILET ROOM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) SINCE THIS IS A CHANGE OF OCCUPANCY, A SERVICE SINK
 IS REQUIRED FOR A MERCANTILE OCCUPANCY PER THE 2014
 FBC-PLBG. TABLE 403.1.
 3) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW
 FOR ALL NEW PLUMBING FIXTURES. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 4) THE LAVATORY IN THE ADA TOILET ROMM AND THE MOP SINK
 SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014
 FBC -PLBG.SEC.607.1.
 5)SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE LAVATORY IN ADA TOILET ROOM PER THE 2014
 FBC-ACCESS.SEC.604.3.1. & SEC. 606.2 & SEC.305.
 6) SHT. A.01 - THE UPDATE MODIFICATION NOTE SHALL
 INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP
 SINK AND THE REQUIREMENT FOR HOT WATER TO THE SCOPE OF
 WORK. WPB AMEND.TO FBC 107.2.1
 7) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES TO THE CENTERLINE FROM THE FRONT OF THE WATER
 CLOSET. 2014 FBC-ACCESS SEC.604.7.
 8) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC. 307.2. FOR PROTRUSION LIMITS. A SKIRT
 ON THE DRINKING FOUNTAINS MAY BE REQUIRED TO COMPLY.
 SUBMIT MANUF. SPCIFICATION SHEETS FOR THE ACCESSIBLE
 DRINKING FOUNTAIN THAT CLEARLY SHOWS THE HEIGHT OF THE
 LEADING EDGES OF THE UNIT. WPB AMEND. TO FBC SEC.
 107.2.1.
 9) TWO SETS OF PLANS REQUIRED WPB AMEND. TO FBC
 SEC107.1 THREE SETS OF PLANS HAVE BEEN VOIDED AND ONE
 HAS NOT LEAVING OMLY ONE SET FOR REVIEW.