2015-10-13 06:59:19 | 1ST REVIEW: FBC 2014 |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |
| |
| |
| |
| PLUMBING COMMENTS: |
| |
| 1.SHOW CLEAR FLOOR SPACE FOR LAVATORY IN ACCESSIBLE |
| BATHROOM. |
| PER WPB AMEN. SEC 107.2.1 |
| 2.GRAB BARS SHALL COMPLY WITH.FBC ACC SEC 609.4 |
| POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR |
| CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE |
| INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM) |
| MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE |
| HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A |
| BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1. |
| 3.TOILET SHALL COMPLY WITH FBC ACC.SEC 604.2 LOCATION. |
| THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION, |
| 4. A DRINKING FOUNTAIN IS REQUIRED TO COMPLY WITH FBC |
| ACC. SEC |
| 211.2 MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| FOUNTAINS. |
| |
| 5.PROVIDE SANITARY AND WATER RISER DIAGRAM. |
| PER WPB AMEN. 107 .3.5.1.3(13) |
| THE FOLLOWING IS AN UPDATED PLUMBING REVIEW AS OF |
| 12/9/15; |
| 1) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR |
| PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK |
| BEING DONE TO THE EXISTING TOILET ROOM. WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 2) SINCE THIS IS A CHANGE OF OCCUPANCY, A SERVICE SINK |
| IS REQUIRED FOR A MERCANTILE OCCUPANCY PER THE 2014 |
| FBC-PLBG. TABLE 403.1. |
| 3) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW |
| FOR ALL NEW PLUMBING FIXTURES. WPB AMEND. TO FBC SEC. |
| 107.3.5.1.3. |
| 4) THE LAVATORY IN THE ADA TOILET ROMM AND THE MOP SINK |
| SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014 |
| FBC -PLBG.SEC.607.1. |
| 5)SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER |
| CLOSET AND THE LAVATORY IN ADA TOILET ROOM PER THE 2014 |
| FBC-ACCESS.SEC.604.3.1. & SEC. 606.2 & SEC.305. |
| 6) SHT. A.01 - THE UPDATE MODIFICATION NOTE SHALL |
| INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP |
| SINK AND THE REQUIREMENT FOR HOT WATER TO THE SCOPE OF |
| WORK. WPB AMEND.TO FBC 107.2.1 |
| 7) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 |
| INCHES TO THE CENTERLINE FROM THE FRONT OF THE WATER |
| CLOSET. 2014 FBC-ACCESS SEC.604.7. |
| 8) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 |
| FBC-ACCESS. SEC. 307.2. FOR PROTRUSION LIMITS. A SKIRT |
| ON THE DRINKING FOUNTAINS MAY BE REQUIRED TO COMPLY. |
| SUBMIT MANUF. SPCIFICATION SHEETS FOR THE ACCESSIBLE |
| DRINKING FOUNTAIN THAT CLEARLY SHOWS THE HEIGHT OF THE |
| LEADING EDGES OF THE UNIT. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 9) TWO SETS OF PLANS REQUIRED WPB AMEND. TO FBC |
| SEC107.1 THREE SETS OF PLANS HAVE BEEN VOIDED AND ONE |
| HAS NOT LEAVING OMLY ONE SET FOR REVIEW. |