2015-11-05 11:53:131ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100233
 11/5/2015
  
 1) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
 IN ACCORDANCE WITH THIS SECTION PLEASE PROVIDE ENERGY
 CALCULATIONS- SEE THE FOLLOWING SECTIONS FOR COMPLIANCE
 SUBMITTAL INFORMATION: C101.5.1 COMPLIANCE MATERIALS.
 THE FLORIDA BUILDING COMMISSION SHALL APPROVE SPECIFIC
 COMPUTER SOFTWARE. THE CODE OFFICIAL SHALL BE PERMITTED
 TO APPROVE WORKSHEETS, COMPLIANCE MANUALS AND OTHER
 SIMILAR MATERIALS THAT MEET THE INTENT OF THIS CODE.
 C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING
 SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS
 MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN
 APPENDIX C.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS ON
 THE PLAN IN ACCORDANCE WUITH TABLE 403.3 FBC-14
 MECHANICAL. THE CALCULATIONS SHALL INDICATE THE AMOUNT
 OF CFM'S OF OUTSIDE AIR REQUIRED FOR THE RETAIL SPACE
 OCCUPANTS, AND THE AMOUNT OF CFM'S PROVIDED BY THE
 EXISTING OR PROPOSED SYSTEMS.
 3) MECHANICAL EXHAUST IS REQUIRED FOR THE NEW TOILET
 ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER