Plan Review Notes For Permit 15100194 |
Permit Number |
15100194 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-10 10:44:29 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. ENGINEER STATES REQUIRED OPENINGS FOR BEDROOM | | EGRESS, BUT THE WINDOWS SHOWN ON THE ENGINEER'S FLOOR | | PLAN DO NOT COMPLY WITH THESE REQUIREMENTS. PLEASE | | CLARIFY, FBC 107. DESIGNER'S INTENT IS NOT CLEAR, CODE | | COMPLIANCE IS NOT CLEAR. | | | | 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND | | OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 704.1. THE | | CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%. | | | | TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION | | NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN | | HEIGHT: | | | | STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS | | - AWNING, CASEMENT, SINGLE HUNG? | | | | STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE. | | CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE | | WINDOW IS FULLY OPEN. | | | | STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE. | | THIS CAN BE OBTAINED FROM THE MANUFACTURER. | | | | 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | FAC9N-3, FBC 5TH EDITION RESIDENTIAL 301. PROVIDE THE | | FLORIDA STATE PRODUCT APPROVAL COVER SHEET FOR THE | | DOOR, WWW.FLORIDABUILDING.ORG. THIS WILL SHOW THE | | APPROVAL NUMBER, CODE VERSION, STATUS, AND OTHER | | INFORMATION. | | | | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | 109. | | | | |
|