2015-11-09 17:23:45 | RESIDENTIAL (R3) REAR BUILDING ALTERATION BUILDING |
| REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- THERE ARE NOT DRAWINGS SHOWING THE SCOPE OF WORK |
| SPECIFIED ON THE PERMIT APPLICATION. PROVIDE COMPLETE |
| FLOOR PLANS SHOWING ALL THE SCOPE OF WORK DESCRIBED IN |
| THE PERMIT APPLICATION. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. CLEARLY SPECIFY ALL SCOPE OF WORK, INCLUDING THE |
| REBUILDING OF THE EXTERIOR STAIRCASE. REVISE SCOPE OF |
| WORK AND VALUATION ON THE PERMIT APPLICATION. VALUATION |
| TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD |
| AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED |
| BY SEC. 109.3 CITY AMENDMENTS. . PROVIDE COPIES OF |
| SIGNED CONTRACTS FOR CONTRACTOR'S FEES AND FOR DESIGN |
| PROFESSIONAL FEES. |
| |
| 3- SHEET S2.00: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| FRAMING OF THE HANDRAIL AND GUARDRAIL TO SHOW |
| COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). CLEARLY SPECIFY |
| ALL CONNECTORS. |
| |
| B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| RECONSTRUCTION OF THE STAIRCASE. CLEARLY SPECIFY ALL |
| FRAMING MEMBERS AND CONNECTORS. PROVIDE COMPLETE |
| LANDING FRAMING PLAN. PROVIDE EXTERIOR SECTION DETAIL |
| THAT MATCHES ACTUAL CONSTRUCTION. THERE ARE NO |
| CONNECTIONS TO FLOOR TRUSSES. SPECIFY ALL CONNECTIONS |
| AT TOP AND BOTTOM OF STAIRS. SEC. R301 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR ALL SIMPSON STRUCTURAL |
| CONNECTORS SPECIFIED ON THE DETAILS. PROVIDE ONLY THE |
| FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING |
| THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD TO |
| SPECIFY THE FLORIDA PRODUCT APPROVAL NEXT TO EACH |
| SPECIFIED CONNECTOR. |
| |