2016-02-25 15:07:32 | 3RD REVIEW 2014 5TH FBC ED. NEC 2011/RESIDENTIAL |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6713 |
| [email protected] |
| |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| 1 PLEASE CLARIFY THE INTENT OF HOW SE CABLE IS BEING |
| RAN FOR 2 MAJOR REASONS ONE IS THE TERMINATIONS OF |
| ALUMINUM CONDUCTORS INTO THE EQUIPMENT LUGS NEC 110.14 |
| A & THE OTHER IS THE THERMAL INSULATION TEMPERATURE |
| LIMITATION TO THE 60 DEGREE COLUMN NEC 338. |
| 2 PROVIDE AN INTERSYSTEM BONDING STRIP NEC 250.94 |
| 3 PROVIDE SERVICE ENTRANCE CONDUCTORS SIZES TO MEET |
| LOAD DEMANDS ALSO STATE IF SERVICE EQUIPMENT HAS A MAIN |
| DISCONNECT. NEC 230, |
| 4 IN BATHROOMS GFCI MUST BE WITHIN 3 FT OF EACH OUTSIDE |
| EDGE BASIN. NEC 210.52 D (DOUBLE SINKS REQUIRE EITHER 2 |
| ON EACH SIDE OR 1 IN THE MIDDLE TO BE COMPLIANT.) |
| 5 SHOW PANEL LOCATIONS ON ELECTRICAL FLOOR PLAN AS WELL |
| AS WH & AC DISCONNECTS. WBA 107 |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| |