2015-12-23 18:58:08 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6700 |
| [email protected] |
| ALTERNATE CONTACT |
| MIKE ALBARRAN |
| 561-805-6746 |
| [email protected] |
| |
| |
| PROVIDE 2 SETS OF PLANS AS REQUIRED BY CITY OF WEST |
| PALM BEACH FBC 107 |
| PROPERLY LABEL EACH AREA AND PROVIDE SCOPE OF WORK PER |
| CWPB FBC 107 |
| SHOW SERVICE LOCATION ON FLOOR PLANS AND SHOW PROPER |
| GROUNDING AND BONDING ON RISER , NEC 250.53 WATER/METAL |
| PIPE , NEC 250.94 INTERSYSTEM. |
| SHOW HOW SE CABLE IS BEING RAN AS YOUR FEEDER |
| CONDUCTORS NEC 338 |
| TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11 |
| R404.1 LIGHTING EQUIPMENT (MANDATORY). |
| A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH |
| EFFICACY LAMPS. |
| R402.4.4 RECESSED LIGHTING. |
| RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN |
| AIR LEAKAGE RATE NOT MORE THAN 2.0 CFM (0.944 L/S) WHEN |
| TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF (75 |
| PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES |
| SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE |
| HOUSING AND THE INTERIOR WALL OR CEILING COVERING. |
| ALL RECESSED LIGHTING OVER SHOWER OR BATHTUB SHALL BE |
| VAPOR TIGHT. |