2015-12-23 18:58:081ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 PROVIDE 2 SETS OF PLANS AS REQUIRED BY CITY OF WEST
 PALM BEACH FBC 107
 PROPERLY LABEL EACH AREA AND PROVIDE SCOPE OF WORK PER
 CWPB FBC 107
 SHOW SERVICE LOCATION ON FLOOR PLANS AND SHOW PROPER
 GROUNDING AND BONDING ON RISER , NEC 250.53 WATER/METAL
 PIPE , NEC 250.94 INTERSYSTEM.
 SHOW HOW SE CABLE IS BEING RAN AS YOUR FEEDER
 CONDUCTORS NEC 338
 TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11
 R404.1 LIGHTING EQUIPMENT (MANDATORY).
 A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS.
 R402.4.4 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN
 AIR LEAKAGE RATE NOT MORE THAN 2.0 CFM (0.944 L/S) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF (75
 PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES
 SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE
 HOUSING AND THE INTERIOR WALL OR CEILING COVERING.
 ALL RECESSED LIGHTING OVER SHOWER OR BATHTUB SHALL BE
 VAPOR TIGHT.