2016-01-05 07:56:46 | RESIDENTIAL (R3) MAIN HOUSE ALTERATION SECOND BUILDING |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- PLANS SUBMITTED ARE NOT ELECTRONICALLY TRANSMITTED |
| PLANS. ENGINEER NEEDS TO PROVIDE ORIGINAL SEAL AND |
| SIGNATURE ON ALL PLANS AS REQUIRED BY 61G15-23.002 AND |
| CHAPTER 471 F.S. |
| RESPONSE: ONLY ONE SET OF DRAWINGS WAS SUBMITTED. NEED |
| TO PROVIDE TWO COMPLETE SETS OF PLANS. SEC. 107.1 CITY |
| AMENDMENTS. |
| |
| 2- REVISED DRAWINGS SHOW CLOUDS WITH A DARK BACKGROUND |
| ON ALL THE REVISED INFORMATION. DARK BACKGROUND ON THE |
| CLOUDS WILL NOT ALLOW THE INFORMATION TO BE READ WHEN |
| THE DRAWINGS ARE SCANNED. PLEASE RE-SUBMIT DRAWINGS |
| WITHOUT THE DARK BACKGROUND ON THE CLOUDS. DRAWINGS |
| NEED TO BE CLEAR FOR RECORD RETENTION PURPOSES. SEC. |
| 107.2.1.4 CITY AMENDMENTS. |
| |
| 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| 4- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. A/C EQUIPMENT |
| SIZING CALCULATIONS WERE SUBMITTED. NOT ENERGY |
| CALCULATIONS WERE SUBMITTED. |
| |