2015-11-09 16:30:59RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE IS NO COORDINATION WITH EQUIPMENT SIZING
 CALCULATIONS AND FLOOR PLAN ON SHEET M1.00 SUBMITTED.
 SHEET M1.00 SHOWS ONLY ONE A/C UNIT. EQUIPMENT. ALSO,
 EQUIPMENT LISTED ON THE A/C PLAN DOESN'T MATCH
 EQUIPMENT SIZING CALCULATIONS. PROVIDE EQUIPMENT SIZING
 CALCULATIONS THAT MATCH A/C PLAN. SEC. 107.2.. 1 CITY
 AMENDMENTS.
  
 2- CONDENSING UNIT MOUNTING DETAIL SHOWN ON SHEET M1.00
 IS INADEQUATE. (4) 2 1/4" TAPCONS ARE NOT ENOUGH
 SPECIFICATIONS TO HOLD THE CONDENSING UNIT. PROVIDE A
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW IS THE
 CONDENSING UNIT ATTACHED TO RESIST THE WIND LOADS OF
 SEC. R301 OF FBC-RESIDENTIAL.
 AND, CLEARLY SPECIFY LOCATION OF ALL CONNECTORS.
  
 3- DRAWING M1.00 : PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE RETURN AIR
 SEC. M1602 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 SPECIFY SIZE OF GRILL SHOWN ON THE FIRST FLOOR AND
 SECOND FLOOR AND SPECIFY HOW ARE THE RETURN GRILLS
 CONNECTED TO THE AIR HANDLER UNIT.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE BALANCED RETURN AIR SEC. M1602.4 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014) FOR ALL THE
 BEDROOMS ON THE SECOND FLOOR.
  
 5- PLANS SUBMITTED ARE NOT ELECTRONICALLY TRANSMITTED
 PLANS. ENGINEER NEEDS TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE ON ALL PLANS AS REQUIRED BY 61G15-23.002 AND
 CHAPTER 471 F.S.
  
  