2015-11-09 16:30:59 | RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- THERE IS NO COORDINATION WITH EQUIPMENT SIZING |
| CALCULATIONS AND FLOOR PLAN ON SHEET M1.00 SUBMITTED. |
| SHEET M1.00 SHOWS ONLY ONE A/C UNIT. EQUIPMENT. ALSO, |
| EQUIPMENT LISTED ON THE A/C PLAN DOESN'T MATCH |
| EQUIPMENT SIZING CALCULATIONS. PROVIDE EQUIPMENT SIZING |
| CALCULATIONS THAT MATCH A/C PLAN. SEC. 107.2.. 1 CITY |
| AMENDMENTS. |
| |
| 2- CONDENSING UNIT MOUNTING DETAIL SHOWN ON SHEET M1.00 |
| IS INADEQUATE. (4) 2 1/4" TAPCONS ARE NOT ENOUGH |
| SPECIFICATIONS TO HOLD THE CONDENSING UNIT. PROVIDE A |
| COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW IS THE |
| CONDENSING UNIT ATTACHED TO RESIST THE WIND LOADS OF |
| SEC. R301 OF FBC-RESIDENTIAL. |
| AND, CLEARLY SPECIFY LOCATION OF ALL CONNECTORS. |
| |
| 3- DRAWING M1.00 : PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING COMPLIANCE WITH THE RETURN AIR |
| SEC. M1602 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| SPECIFY SIZE OF GRILL SHOWN ON THE FIRST FLOOR AND |
| SECOND FLOOR AND SPECIFY HOW ARE THE RETURN GRILLS |
| CONNECTED TO THE AIR HANDLER UNIT. |
| |
| 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| COMPLIANCE WITH THE BALANCED RETURN AIR SEC. M1602.4 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014) FOR ALL THE |
| BEDROOMS ON THE SECOND FLOOR. |
| |
| 5- PLANS SUBMITTED ARE NOT ELECTRONICALLY TRANSMITTED |
| PLANS. ENGINEER NEEDS TO PROVIDE ORIGINAL SEAL AND |
| SIGNATURE ON ALL PLANS AS REQUIRED BY 61G15-23.002 AND |
| CHAPTER 471 F.S. |
| |
| |