2015-10-21 12:56:282ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100135
 10/21/15
  
 1) THE ENERGY EFFICIENCY COMPLIANCE FORM R402-2014 IS
 NOT FILLED OUT COMPLETELY. PLEASE COMPLETE TABLES R402A
 AND R402 B.
 2) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE A
 RETURN AIR SYSTEM: INDICATE HOW AIR SUPPLIED TO THE
 BEDROOMS, AND OTHER ROOMS OR SPACES WILL BE RETURNED TO
 THE AIR HANDLER.
 3) THE SUPPLY DUCT SIZES APPEAR TO BE TOO SMALL: THE 6"
 SHOULD BE 8", THE 8" SHOULD BE 10". PLEASE INDICATE HOW
 THE DUCTS WERE SIZED.
 4) AS PREVIOUSLY REQUESTED, PROVIDE STRUCTURAL DETAILS
 FOR INSTALLATION OF THE CONDENSER PAD, AND ENGINEERED
 WIND LOAD TIE DOWN DETAILS FOR MOUNTING THE CONDENSER
 TO THE PAD.
 5) AS PREVIOUSLY REQUESTED, CONTRACTOR PLANS REQUIRE A
 SIGNATURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER