Plan Review Notes For Permit 15100135 |
Permit Number |
15100135 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-10-21 12:56:28 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15100135 | | 10/21/15 | | | | 1) THE ENERGY EFFICIENCY COMPLIANCE FORM R402-2014 IS | | NOT FILLED OUT COMPLETELY. PLEASE COMPLETE TABLES R402A | | AND R402 B. | | 2) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE A | | RETURN AIR SYSTEM: INDICATE HOW AIR SUPPLIED TO THE | | BEDROOMS, AND OTHER ROOMS OR SPACES WILL BE RETURNED TO | | THE AIR HANDLER. | | 3) THE SUPPLY DUCT SIZES APPEAR TO BE TOO SMALL: THE 6" | | SHOULD BE 8", THE 8" SHOULD BE 10". PLEASE INDICATE HOW | | THE DUCTS WERE SIZED. | | 4) AS PREVIOUSLY REQUESTED, PROVIDE STRUCTURAL DETAILS | | FOR INSTALLATION OF THE CONDENSER PAD, AND ENGINEERED | | WIND LOAD TIE DOWN DETAILS FOR MOUNTING THE CONDENSER | | TO THE PAD. | | 5) AS PREVIOUSLY REQUESTED, CONTRACTOR PLANS REQUIRE A | | SIGNATURE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|