2015-10-14 12:05:25 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15100135 |
| 10/14/15 |
| |
| 1) THE PERMIT APPLICATION WORK DESCRIPTION IS |
| INCORRECT: THIS IS NOT A CHANGE-OUT, IT IS A NEW AC |
| SYSTEM IN A PREVIOUSLY UNCONDITIONED BUILDING. PLEASE |
| CHANGE THE DESCRIPTION ON THE APPLICATION. |
| 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY |
| CONSERVATION: CHANGE IN SPACE CONDITIONING. |
| ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME |
| CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO |
| FULL COMPLIANCE WITH THIS CODE. |
| PLEASE PROVIDE TWO COPIES OF ENERGY CALCULATIONS USING |
| EITHER THE PRESCRIPTIVE OR PERFORMANCE COMPLIANCE PATH- |
| SEE TABLE R101.5.1 FOR FORMS. |
| 3) REFER TO SECTION 403.6.1 AND PROVIDE AC COOLING AND |
| HEATING CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL J. |
| 4) THE SUBMITTED AC PLAN DOES NOT CLEARLY SHOW WHERE |
| THE NEW AIR HANDLER IS TO BE LOCATED- PLEASE CLARIFY, |
| AND NOTE THAT AIR HANDLERS SHALL NOT BE INSTALLED IN |
| THE ATTIC WHEN A PLAN IS BROUGHT INTO COMPLIANCE USING |
| THE PRESCRIPTIVE METHOD- SEE R402. |
| 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE |
| CONDENSER PAD, AND WIND LOAD TIE DOWN DETAILS FOR |
| ANCHORING THE CONDENSER TO THE PAD- REFER TO SECTIONS |
| M1305.1.4.1 AND M1401.4 FBC-14 RESIDENTIAL. |
| 6) IDENTIFY ALL ROOMS ON THE LAYOUT PLAN AND SHOW A |
| MEANS OF RETURN AIR FROM REQUIRED ROOMS AND SPACES- |
| REFER TO SECTION M1602 FBC-14 RESIDENTIAL. |
| 7) AN ELECTRICAL PLAN AND LOAD CALCULATIONS IS |
| REQUIRED. |
| 8) PLEASE NOTE THAT ALL CONTRACTOR PLANS MUST BE SIGNED |
| BY THE CONTRACTOR THAT DREW THEM- SECTIO N 107.2.1 WPB |
| AMENDMENTS TO THE FBC-10 BUILDING. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |