Plan Review Notes
Plan Review Notes For Permit 15100135
Permit Number 15100135
Review Stop M
Sequence Number 1
Notes
Date Text
2015-10-14 12:05:251ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100135
 10/14/15
  
 1) THE PERMIT APPLICATION WORK DESCRIPTION IS
 INCORRECT: THIS IS NOT A CHANGE-OUT, IT IS A NEW AC
 SYSTEM IN A PREVIOUSLY UNCONDITIONED BUILDING. PLEASE
 CHANGE THE DESCRIPTION ON THE APPLICATION.
 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY
 CONSERVATION: CHANGE IN SPACE CONDITIONING.
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE.
 PLEASE PROVIDE TWO COPIES OF ENERGY CALCULATIONS USING
 EITHER THE PRESCRIPTIVE OR PERFORMANCE COMPLIANCE PATH-
 SEE TABLE R101.5.1 FOR FORMS.
 3) REFER TO SECTION 403.6.1 AND PROVIDE AC COOLING AND
 HEATING CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL J.
 4) THE SUBMITTED AC PLAN DOES NOT CLEARLY SHOW WHERE
 THE NEW AIR HANDLER IS TO BE LOCATED- PLEASE CLARIFY,
 AND NOTE THAT AIR HANDLERS SHALL NOT BE INSTALLED IN
 THE ATTIC WHEN A PLAN IS BROUGHT INTO COMPLIANCE USING
 THE PRESCRIPTIVE METHOD- SEE R402.
 5) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE
 CONDENSER PAD, AND WIND LOAD TIE DOWN DETAILS FOR
 ANCHORING THE CONDENSER TO THE PAD- REFER TO SECTIONS
 M1305.1.4.1 AND M1401.4 FBC-14 RESIDENTIAL.
 6) IDENTIFY ALL ROOMS ON THE LAYOUT PLAN AND SHOW A
 MEANS OF RETURN AIR FROM REQUIRED ROOMS AND SPACES-
 REFER TO SECTION M1602 FBC-14 RESIDENTIAL.
 7) AN ELECTRICAL PLAN AND LOAD CALCULATIONS IS
 REQUIRED.
 8) PLEASE NOTE THAT ALL CONTRACTOR PLANS MUST BE SIGNED
 BY THE CONTRACTOR THAT DREW THEM- SECTIO N 107.2.1 WPB
 AMENDMENTS TO THE FBC-10 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved