2017-05-16 13:40:01 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 15100102 SUBMITTAL |
| W. P. B. PERMIT: 15100101 ROOFING/ SUB-PERMIT |
| MASTER: 14120431 |
| ADD: 312 23RD ST. |
| CONT: THERMA SEAL ROOF |
| TEL: (561) 223-2096 |
| E-MAIL: [email protected] |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 3RD REVIEW |
| DATE: TUES. MAY 16/ 2017 |
| ACTION: DENIED |
| |
| HISTORY: |
| 1ST REVIEW: TUES. OCT. 06/ 2015 15100101 ROOFING |
| SUB-PERMIT & 15100102 SUBMITTAL: DENIED |
| |
| 2ND REVIEW: TUES. JAN. 19/ 2016 2015 15100101 ROOFING |
| SUB-PERMIT: BUILDING PROVISO. |
| THE ROOFING SUB-PERMIT WAS ISSUED WITH THE PROVISO THAT |
| PULL TEST WERE TO BE COMPLETED AS PER |
| TAS-105 TO VERIFY THE ASSUMPTIONS AND VALUES TAKEN BY |
| THE ENGINEERING FIRM FORENSIC ENGINEERING. |
| |
| 3RD REVIEW: TUES. MAY 16/ 2017 ROOF COMPLETED, NO |
| ROOFING APPROVALS APPROVED, NO SUBMITTALS FOR PULL TEST |
| TO VERIFY ASSUMPTIONS. |
| |
| THE DESIGNER OF RECORD SUBMITTED A COVERSHEET |
| INDICATING HE HAS REVIEWED THE SUBMITTALS BUT DOES NOT |
| INCLUDE THE SUBMITTALS APPROVED UNDER THIS COVER |
| LETTER, REVIEWED BY HPA ORLANDO. SUBMITTALS (ALL 7) |
| SHOW APPROVAL BY THE CONTRACTOR OF RECORD BRADLEY |
| CONSTRUCTION WITH NO EXCEPTIONS TAKEN. |
| |
| 1) THE SUBMITTED ENGINEERS REPORT FROM FORENSIC |
| ENGINEERING CONSULTANTS REFERENCES THE MIAMI-DADE NOA |
| 13-0129.16 A JOHNS MANVILLE MODIFIED BITUMEN SBS ROOF |
| SYSTEM OVER LIGHT WEIGHT CONCRETE DECK. THE REPORT |
| RECOMMENDS TESTING TO TAS-105 TO VERIFY ASSUMPTIONS. |
| UNTIL THE PULL OUT TEST IS PREFORMED, THE VALUES IN THE |
| FORENSIC ENGINEERING ARE ONLY ASSUMPTIONS. PLEASE REFER |
| TO TAS -105 SECTION 8, 8.1- 8.3 FOR THE AMOUNT OF TEST |
| TO BE PERFORMED. *.3 SAMPLE TEST FOR LIGHTWEIGHT |
| CONCRETE SHALL BE INCREASED BY 125 %. ALSO NOTE 8.4 |
| -8.6 FOR FURTHER INFORMATION . |
| |
| TO VIEW THE 2010 TAS REQUIREMENTS GO TO: |
| HTTPS://FLORIDABUILDING.ORG |
| CLICK ON: FLORIDA BUILDING CODE |
| 8. TEST PROCEDURE FOR ANCHOR OR BASE SHEET, INSULATION, |
| AND MEMBRANE ATTACHMENT TESTING |
| 8.1 ON ROOF DECKS OF 100 SQUARES OR LESS, TEN (10) |
| WITHDRAWAL RESISTANCE TESTS SHALL BE CONDUCTED, NOT |
| LESS THAN THREE (3) OF WHICH SHALL BE IN THE PERIMETER |
| AREAS (2), THREE (3) IN CORNER AREAS (3), THE |
| REMAINDERS IN THE FIELD AREAS (1) AS DEFINED IN ASCE 7. |
| 8.2 FOR EVERY ADDITIONAL 50 SQUARES, AN ADDITIONAL |
| THREE (3) WITHDRAWAL RESISTANCE TESTS SHALL BE |
| CONDUCTED. (THIS RATIO OF 50:3 SHALL BE MAINTAINED WITH |
| EACH ADDITIONAL INCREASE IN SAMPLES.) |
| 8.3 THE NUMBER OF TEST SAMPLES REQUIRED IN SHALL BE |
| INCREASED BY 125% FOR ALL GYPSUM, LIGHTWEIGHT |
| INSULATING CONCRETE AND CEMENTITIOUS WOOD FIBER DECK |
| TYPES. |
| |
| 8.4 TESTING SHALL ALSO TAKE PLACE IN ANY LOW AREAS THAT |
| ARE, OR MAY BE, SUBJECTED TO PONDING WATER. ALL SUCH |
| AREAS SHALL BE NOTED ON A ROOF PLAN ATTACHED TO THE |
| FINAL TEST REPORT. |
| 8.5 IF MORE THAN ONE DECK TYPE IS ON A SINGLE ROOF |
| AREA, EACH DECK TYPE SHALL BE TREATED AS A SEPARATE |
| ROOF AREA. |
| 8.6 STAIR TOWERS, MECHANICAL PENTHOUSES AND MECHANICAL |
| ROOMS SHALL HAVE A MINIMUM OF FOUR (4) WITHDRAWAL |
| RESISTANCE TESTS, TWO OF WHICH SHALL BE TAKEN AT |
| PERIMETER AREAS 2 & 3, AS DEFINED IN ASCE 7. |
| |
| 2) TESTING TO BE COMPLETED BY A QUALIFIED TESTING |
| COMPANY, AND THE RESULTS OF THE PULL TEST ARE |
| SUMMARIZED IN A REPORT, THE PULL TEST, FORENSIC |
| ENGINEERING CALCULATIONS AND NOA 13-0129.16 ARE TO BE |
| REVIEWED BY THE ENGINEER OF RECORD FOR CODE COMPLIANCE |
| SHOP DRAWING STAMP OF APPROVAL ONCE REVIEWED AND |
| ACCEPTED, THEN SUBMITTED TO THE BUILDING DEPARTMENT FOR |
| REVIEW. |
| |
| |
| 3) FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW. |
| |
| 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD (SHOP DRAWING STAMP OF APPROVAL) PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 5) THIS REVIEW SOME OF THE SUBMITTED DOCUMENTS, PRODUCT |
| APPROVALS WERE COPIED SO SMALL THEY MAY NOT BE LEGIBLE |
| WHEN SCANNED TO RECORD RETENTION. 107.2.1.4 QUALITY OF |
| BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH |
| THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS |
| AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO |
| ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, |
| OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE |
| REQUIREMENTS OF FLORIDA STATUTES. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |