Plan Review Notes
Plan Review Notes For Permit 15100102
Permit Number 15100102
Review Stop B
Sequence Number 2
Notes
Date Text
2017-05-16 13:40:01BUILDING PLAN REVIEW
 W. P. B. REVISION: 15100102 SUBMITTAL
 W. P. B. PERMIT: 15100101 ROOFING/ SUB-PERMIT
 MASTER: 14120431
 ADD: 312 23RD ST.
 CONT: THERMA SEAL ROOF
 TEL: (561) 223-2096
 E-MAIL: [email protected]
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: TUES. MAY 16/ 2017
 ACTION: DENIED
  
 HISTORY:
 1ST REVIEW: TUES. OCT. 06/ 2015 15100101 ROOFING
 SUB-PERMIT & 15100102 SUBMITTAL: DENIED
  
 2ND REVIEW: TUES. JAN. 19/ 2016 2015 15100101 ROOFING
 SUB-PERMIT: BUILDING PROVISO.
 THE ROOFING SUB-PERMIT WAS ISSUED WITH THE PROVISO THAT
 PULL TEST WERE TO BE COMPLETED AS PER
 TAS-105 TO VERIFY THE ASSUMPTIONS AND VALUES TAKEN BY
 THE ENGINEERING FIRM FORENSIC ENGINEERING.
  
 3RD REVIEW: TUES. MAY 16/ 2017 ROOF COMPLETED, NO
 ROOFING APPROVALS APPROVED, NO SUBMITTALS FOR PULL TEST
 TO VERIFY ASSUMPTIONS.
  
 THE DESIGNER OF RECORD SUBMITTED A COVERSHEET
 INDICATING HE HAS REVIEWED THE SUBMITTALS BUT DOES NOT
 INCLUDE THE SUBMITTALS APPROVED UNDER THIS COVER
 LETTER, REVIEWED BY HPA ORLANDO. SUBMITTALS (ALL 7)
 SHOW APPROVAL BY THE CONTRACTOR OF RECORD BRADLEY
 CONSTRUCTION WITH NO EXCEPTIONS TAKEN.
  
 1) THE SUBMITTED ENGINEERS REPORT FROM FORENSIC
 ENGINEERING CONSULTANTS REFERENCES THE MIAMI-DADE NOA
 13-0129.16 A JOHNS MANVILLE MODIFIED BITUMEN SBS ROOF
 SYSTEM OVER LIGHT WEIGHT CONCRETE DECK. THE REPORT
 RECOMMENDS TESTING TO TAS-105 TO VERIFY ASSUMPTIONS.
 UNTIL THE PULL OUT TEST IS PREFORMED, THE VALUES IN THE
 FORENSIC ENGINEERING ARE ONLY ASSUMPTIONS. PLEASE REFER
 TO TAS -105 SECTION 8, 8.1- 8.3 FOR THE AMOUNT OF TEST
 TO BE PERFORMED. *.3 SAMPLE TEST FOR LIGHTWEIGHT
 CONCRETE SHALL BE INCREASED BY 125 %. ALSO NOTE 8.4
 -8.6 FOR FURTHER INFORMATION .
  
 TO VIEW THE 2010 TAS REQUIREMENTS GO TO:
 HTTPS://FLORIDABUILDING.ORG
 CLICK ON: FLORIDA BUILDING CODE
 8. TEST PROCEDURE FOR ANCHOR OR BASE SHEET, INSULATION,
 AND MEMBRANE ATTACHMENT TESTING
 8.1 ON ROOF DECKS OF 100 SQUARES OR LESS, TEN (10)
 WITHDRAWAL RESISTANCE TESTS SHALL BE CONDUCTED, NOT
 LESS THAN THREE (3) OF WHICH SHALL BE IN THE PERIMETER
 AREAS (2), THREE (3) IN CORNER AREAS (3), THE
 REMAINDERS IN THE FIELD AREAS (1) AS DEFINED IN ASCE 7.
 8.2 FOR EVERY ADDITIONAL 50 SQUARES, AN ADDITIONAL
 THREE (3) WITHDRAWAL RESISTANCE TESTS SHALL BE
 CONDUCTED. (THIS RATIO OF 50:3 SHALL BE MAINTAINED WITH
 EACH ADDITIONAL INCREASE IN SAMPLES.)
 8.3 THE NUMBER OF TEST SAMPLES REQUIRED IN SHALL BE
 INCREASED BY 125% FOR ALL GYPSUM, LIGHTWEIGHT
 INSULATING CONCRETE AND CEMENTITIOUS WOOD FIBER DECK
 TYPES.
  
 8.4 TESTING SHALL ALSO TAKE PLACE IN ANY LOW AREAS THAT
 ARE, OR MAY BE, SUBJECTED TO PONDING WATER. ALL SUCH
 AREAS SHALL BE NOTED ON A ROOF PLAN ATTACHED TO THE
 FINAL TEST REPORT.
 8.5 IF MORE THAN ONE DECK TYPE IS ON A SINGLE ROOF
 AREA, EACH DECK TYPE SHALL BE TREATED AS A SEPARATE
 ROOF AREA.
 8.6 STAIR TOWERS, MECHANICAL PENTHOUSES AND MECHANICAL
 ROOMS SHALL HAVE A MINIMUM OF FOUR (4) WITHDRAWAL
 RESISTANCE TESTS, TWO OF WHICH SHALL BE TAKEN AT
 PERIMETER AREAS 2 & 3, AS DEFINED IN ASCE 7.
  
 2) TESTING TO BE COMPLETED BY A QUALIFIED TESTING
 COMPANY, AND THE RESULTS OF THE PULL TEST ARE
 SUMMARIZED IN A REPORT, THE PULL TEST, FORENSIC
 ENGINEERING CALCULATIONS AND NOA 13-0129.16 ARE TO BE
 REVIEWED BY THE ENGINEER OF RECORD FOR CODE COMPLIANCE
 SHOP DRAWING STAMP OF APPROVAL ONCE REVIEWED AND
 ACCEPTED, THEN SUBMITTED TO THE BUILDING DEPARTMENT FOR
 REVIEW.
  
  
 3) FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD (SHOP DRAWING STAMP OF APPROVAL) PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) THIS REVIEW SOME OF THE SUBMITTED DOCUMENTS, PRODUCT
 APPROVALS WERE COPIED SO SMALL THEY MAY NOT BE LEGIBLE
 WHEN SCANNED TO RECORD RETENTION. 107.2.1.4 QUALITY OF
 BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved