2015-10-06 09:04:49 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 15100102 |
| W. P. B. PERMIT:15100101 ROOFING |
| MASTER: 14120431 |
| ADD: 312 23RD ST. |
| CONT: THERMA SEAL ROOF |
| TEL: (561) 223-2096 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: TUES. OCT, 06/ 2015 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED ENGINEERS REPORT FROM FORENSIC |
| ENGINEERING CONSULTANTS REFERENCES THE MIAMI-DADE NOA |
| 13-0129.16 A JOHNS MANVILLE MODIFIED BITUMEN SBS ROOF |
| SYSTEM OVER LIGHT WEIGHT CONCRETE DECK. THE REPORT |
| RECOMMENDS TESTING TO TAS-105 TO VERIFY ASSUMPTIONS. |
| UNTIL THE PULL OUT TEST IS PREFORMED, THE VALUES IN THE |
| FORENSIC ENGINEERING ARE ONLY ASSUMPTIONS. PLEASE REFER |
| TO TAS -105 SECTION 8, 8.1- 8.3 FOR THE AMOUNT OF TEST |
| TO BE PREFORMED. *.3 SAMPLE TEST FOR LIGHTWEIGHT |
| CONCRETE SHALL BE INCREASED BY 125 %. ALSO NOTE 8.4 |
| -8.6 FOR FURTHER INFORMATION . |
| |
| 2) TESTING TO BE COMPLETED BY A QUALIFIED TESTING |
| COMPANY, AND THE RESULTS OF THE PULL TEST ARE |
| SUMMARIZED IN A REPORT, THE PULL TEST, FORENSIC |
| ENGINEERING CALCULATIONS AND NOA 13-0129.16 ARE TO BE |
| REVIEWED BY THE ENGINEER OF RECORD FOR CODE COMPLIANCE |
| SHOP DRAWING STAMP OF APPROVAL ONCE REVIEWED AND |
| ACCEPTED, THEN SUBMITTED TO THE BUILDING DEPARTMENT FOR |
| REVIEW. |
| |
| FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW. |
| |
| 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |