2015-10-05 11:32:46 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| ELEVATION CERTIFICATE FOR MAIN HOUSE: |
| |
| C2E, ELEVATION OF MECHANICAL EQUIPMENT TO BE ABOVE 7.5, |
| ELEVATION CERTIFICATE STATES ELEVATION IS 6.80. PLEASE |
| NOTE THAT PHOTOGRAPHS SHOW THE MECHANICAL EQUIPMENT |
| ELEVATED ON STANDS. PLEASE REVISE ELEVATION TO STATE |
| ELEVATION OF EQUIPMENT (NOT CONCRETE PAD) AND ALSO |
| REVISE COMMENTS IN SECTION D. |
| |
| SEE INSTRUCTIONS FOR BUILDING PHOTOGRAPHS, PHOTOGRAPHS |
| MUST SHOW THE FOUNDATION WITH REPRESENTATIVE EXAMPLES |
| OF FLOOD OPENINGS OR VENTS. |
| |
| ELEVATION CERTIFICATE FOR POOL HOUSE: |
| |
| A9(D) INDICATES THAT THERE ARE ENGINEERED FLOOD |
| OPENINGS, PLEASE CLARIFY AS TO LOCATION (IN COMMENTS). |
| FLOOD VENTS CAN BE USED ONLY FOR STORAGE, PARKING, AND |
| ACCESS. ONLY THE PORTION OF THE FLOOD VENT WHICH IS |
| BELOW 7.5' CAN BE COUNTED TOWARDS OPENINGS. COMPLIANCE |
| NOT CLEAR. |
| |
| C2(A) STATES FFE IS 7.4, 7.5 REQUIRED. IF SLAB IS 7.5, |
| FLOOD VENTS ARE NOT REQUIRED. |
| |
| SEE INSTRUCTIONS FOR PHOTOGRAPHS, FLOOD VENTS IN WALLS |
| TO BE INCLUDED. |
| |
| SEE INSTRUCTIONS FOR ELEVATION CERTIFICATE, FLOOD VENT |
| PRODUCT APPROVAL TO BE ATTACHED TO THE ELEVATION |
| CERTIFICATE. I HAVE PRINTED THE PRODUCT APPROVAL COVER |
| SHEET AND ATTACHED THE FLOOD VENT INFORMATION TO THE |
| ELEVATION CERTIFICATE FOR THE HOUSE. PLEASE PROVIDE |
| ANOTHER SET FOR THE CABANA, IF APPLICABLE. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |