Plan Review Notes For Permit 15100085 |
Permit Number |
15100085 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-11-25 10:44:15 | 2ND REVIEW FBC 2014 5TH ED. NEC2011 | | | | PLEASE CLEARLY SHOW COMPLIANCE WITH FBC-EC 405.2.4 | | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC-EC 405.2.4 | | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT | | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & | | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING | | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | | | |
|