2015-11-01 13:23:28 | FBC 2014 5TH ED. NEC2011 | | | | NO FULL REVIEW PERFORMED AS ZONING COMMENT RESULTS IN | | AN ALTERNATE DESIGN REQUIRED. | | | | PLEASE CLEARLY COMPLIANCE WITH FBC 505.1 | | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL | | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN | | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME | | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES | | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS | | OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4 | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | | | |
|