2015-11-09 14:37:27 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. G101, INCORPORATE THE INFORMATION IN THE RESPONSE |
| LETTER REGARING THE PERCENTAGE OF OPENINGS FOR EACH |
| WALL INTO THE PLAN IN ORDER TO SHOW COMPLIANCE WITH FBC |
| TABLE 705.8. |
| |
| CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT |
| COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF |
| EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION |
| DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING |
| REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| SEPARATION DISTANCE) BE SHOWN. |
| |
| ONLY EAST FACING NEW WALLS WERE ADDRESSED IN THE |
| RESPONSE LETTER AND SHOW THE DISTANCE TO THE NEW |
| PROPERTY LINE ON SHEET G101. AS THE PROPERTY LINE IS |
| BEING RELOCATED, COMPLIANCE NEEDS TO BE SHOWN FOR THE |
| EXISTING WALLS AND THE NEW WALLS WHICH FACE SOUTH. |
| |
| BASED ON INFORMATION PROVIDED: BEARING WALLS ARE |
| REQUIRED TO BE 3 HOURS. STRUCTURAL FRAME IS REQUIRED TO |
| BE 2 HOURS. PLAN SHOWS THESE WALLS AS 1 HR; PLEASE SEE |
| FBC TABLE 602, FOOTNOTE A AND REVISE. |
| |
| 2. THE ART IN PUBLIC PLACES WAS SENT VIA EMAIL, CITY OF |
| WEST PALM BEACH CODE OF ORDINANCES 78-123, 78-126. |
| |
| THIS REVISION WILL BE ISSUED WITH THE PROVISO THAT, BY |
| DEC 23, 2015, THE APPROVAL WILL BE PROVIDED. PLEASE |
| SEND A COPY OF THE APPROVAL WHEN AVAILABLE VIA EMAIL TO |
| [email protected] IN ORDER TO DOCUMENT THE PERMIT FILE. |
| |
| 3. OK |
| |
| 4. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR |
| TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107, |
| FBC 1609 (SUBMITTAL, NO FEE). |
| |
| 5. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS |
| AND OTHER INDEPENDENT STRUCTURE ELEMENTS REQUIRE |
| SEPARATE PERMITS WHICH WOULD INCLUDE FEES, BUILDING |
| PERMIT APPLICATIONS, PLANS AND REVIEWS. |
| |
| 6. ADVISORY ONLY; SPEC SHEETS IN APPENDIX WERE NOT |
| REVIEWED. |
| |
| 7. PRIOR TO INSTALLATION, SUBMITTALS FOR THE UL |
| ASSEMBLIES WILL BE REQUIRED. THE SUBMITTAL SHOULD |
| INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED |
| TO BE INDICATED. THE SUBMITTAL IS REQUIRED TO BE |
| REVIEWED BY DOR. THE SUBMITTAL IS REQUIRED TO BE |
| APPROVED THROUGH PLAN REVIEW PRIOR TO COMMENCEMENT. |
| |
| 8 TO 13. OK |
| |
| 14. RE-PLAT TO BE FILED WITHIN 45 DAYS OF PERMIT |
| ISSUANCE (AGREEMENT BETWEEN OWNER AND DEVELOPMENT |
| SERVICES). |
| |
| PLEASE PROVIDE THE PLAT BOOK AND PAGE NUMBER WHEN |
| FILED. |
| |
| 15. OK |
| |
| **NEW COMMENT** |
| |
| 16. SIGNATURE PAGE FOR THE DIGITAL PLANS REQUIRED, OR |
| PROVIDE HARDCOPY SIGNED AND SEALED PLANS FOR 14120908 |
| (PLANS SUBMITTED HAD SOME INCONSISTENCIES WITH THE |
| DIGITAL PLANS ISSUED). |
| |
| |
| |