2016-06-21 18:09:27CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS.
 (2) SHOW DUCT SIZES, SUPPLY OUTLET SIZES AND CFM
 QUANTITIES.
 (3) DIFFERENTIATE WHAT IS EXISTING AND WHAT IS NEW.
 (4) PROVIDE EXISTING AHU EQUIPMENT SCHEDULE (TO INCLUDE
 TOTAL CFM).
 (5) PROVIDE EXHAUST DUCT SIZES FOR KITCHEN EXHAUST.
 (6) HAVE ALL MANUFACTURER SPECIFICATION DOCUMENTATION
 FOR KITCHEN EXHAUST AT JOBSITE FOR INSPECTOR TO VERIFY
 INSTALLATION.
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
 (A) FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
 (B) MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 FLORIDA ENERGY CODE FBC 2014
  
 PROVIDE (2) SETS OF SIGNED ENERGY CALCULATIONS (FORM
 R405-2014 AND HEAT LOAD CALCULATIONS). ONLY ONE
 PROVIDED
  
  