Date |
Text |
2015-10-20 11:30:23 | 1ST REVIEW: FBC 2014 5TH ED. |
| |
| PLEASE SEE NOTES IN BUILDING REVIEW AS TO THE CONFLICT |
| BETWEEN THE PROPOSED PLAN WHICH DESIGNATES THE 297 SF |
| PORCH AS A DEN. PLEASE PROVIDE AN ELECTRICAL PLAN FOR |
| THE AREA DESIGNATED AS A DEN AND REGARDING SMOKE |
| DETECTORS AS FOLLOWS: EXISTING OR PROPOSED ELECTRICAL |
| OUTLETS AND LIGHTING TO DEMONSTRATE COMPLIANCE WITH THE |
| FOLLOWING: |
| |
| FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES. |
| IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| TAMPER-RESISTANT RECEPTACLES. |
| |
| FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| |
| FBCRE3901.2.2 SPACING. |
| RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| OUTLET. |
| |
| E3903.3 ADDITIONAL LOCATIONS. |
| AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET |
| SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE |
| EXTERIOR SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE |
| LEVEL ACCESS. |
| |
| FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |