Plan Review Notes
Plan Review Notes For Permit 15100028
Permit Number 15100028
Review Stop E
Sequence Number 1
Notes
Date Text
2015-10-20 11:30:231ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE SEE NOTES IN BUILDING REVIEW AS TO THE CONFLICT
 BETWEEN THE PROPOSED PLAN WHICH DESIGNATES THE 297 SF
 PORCH AS A DEN. PLEASE PROVIDE AN ELECTRICAL PLAN FOR
 THE AREA DESIGNATED AS A DEN AND REGARDING SMOKE
 DETECTORS AS FOLLOWS: EXISTING OR PROPOSED ELECTRICAL
 OUTLETS AND LIGHTING TO DEMONSTRATE COMPLIANCE WITH THE
 FOLLOWING:
  
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE3901.2.2 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 E3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE
 EXTERIOR SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE
 LEVEL ACCESS.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  