Plan Review Notes For Permit 15100028
Permit Number 15100028
Review Stop B
Sequence Number 1
Notes
Date Text
2015-10-20 10:52:491ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE PLAN APPEARS TO PROPOSE CONDITIONING A 297 SF AREA
 OF THE RESIDENCE IDENTIFIED AS A DEN BUT ON RECORD AS A
 PORCH. THE PLAN ASSOCIATED WITH WINDOW REPLACEMENT
 PERMIT 10060887 COMPLETED IN 2010 DOES NOT SHOW THE
 CONSTRUCTION OF WALLS AND WINDOWS AS CONSISTENT WITH
 THE PROPOSED PLAN.
  
 PLEASE PROVIDE INFORMATION AS TO THE EXISTING
 CONSTRUCTION OF THE 27' LONG AND 11' LONG EXTERIOR
 WALLS WHICH ENCLOSE THE 297SF PORCH. INCLUDE THERMAL
 INSULATION INFORMATION FOR THE WALLS AND CEILING.
 ADDITIONALLY PROVIDE AN ENERGY SUBMITTAL. SHOW ALL WORK
 THAT THERE IS NO PERMIT RECORD OF. PLEASE CLARIFY IF
 THERE IS TO BE A DOOR OR OPEN PASS THROUGH FOR THE AREA
 WHERE THE MASTER BEDROOM COMMUNICATES WITH THE PROPOSED
 DEN. PLEASE INDICATE WHAT THE PROPOSED MEANS OF
 EMERGENCY EGRESS IS FOR THE MASTER BEDROOM, IF IT IS
 THE EXISTING WINDOW TAKING THE PLACE OF A FORMER
 EXTERIOR SGD, IT WILL HAVE TO MEET THE REQUIREMENTS FOR
 NEW CONSTRUCTION.
  
 FBC 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES.
 R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE GRADE FLOOR OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5 SQUARE FEET
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 THE CLAIMED VALUE APPEARS TO BE LOW FOR THE WORK
 PROPOSED AND ESPECIALLY AS THE RECORD DOES NOT
 DEMONSTRATE POSSIBLE PREVIOUS WORK TO ENCLOSE THE
 SCREEN ROOM TO A DEN AND MASTER SITTING ROOM.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLEASE BE ADVISED IF PREVIOUS NON-PERMITTED WORK IS
 PROPOSED TO REMAIN IN PLACE, THEN PURSUANT TO FBC 117 -
 THE BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS
 AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE
 AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED
 TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  