Plan Review Notes
Plan Review Notes For Permit 15100011
Permit Number 15100011
Review Stop M
Sequence Number 2
Notes
Date Text
2015-11-19 13:51:502ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100011
 11/19/15
  
 SEVERAL COMMENTS FROM THE 1ST REVIEW WERE NOT
 ADDRESSED. I AM RE-PRINTING THEM BELOW FOR RESPONSE.
  
 1) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 C101.2 AND C101.4.3 FBC-14 ENERGY CONSERVATION.
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING
 809.1 RECONFIGURED OR CONVERTED SPACES.
 ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL
 SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN
 ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR
 MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL.
 EXCEPTION: EXISTING MECHANICAL VENTILATION SYSTEMS
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 809.2.
 809.2 ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 PLEASE PROVIDE VENTILATION CALCULATIONS IN COMPLIANCE
 WITH TABLE 403.3 FBC-14 MECHANICAL. THE CALCULATIONS
 SHALL INDICATE THE AMOUNT OF OUTSIDE AIR CFM'S
 REQUIRED, AND THE AMOUNT OF OUTSIDE AIR CFM'S BEING
 PROVIDED EITHER BY THE EXISTING OR MODIFIED HVAC
 SYSTEMS.
 3) PLEASE PROVIDE MECHANICAL PLANS INDICATING ALL
 PROPOSED ALTERATIONS TO THE EXISTING HVAC SYSTEMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  