2015-11-19 13:51:50 | 2ND REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15100011 |
| 11/19/15 |
| |
| SEVERAL COMMENTS FROM THE 1ST REVIEW WERE NOT |
| ADDRESSED. I AM RE-PRINTING THEM BELOW FOR RESPONSE. |
| |
| 1) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH |
| C101.2 AND C101.4.3 FBC-14 ENERGY CONSERVATION. |
| 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING |
| 809.1 RECONFIGURED OR CONVERTED SPACES. |
| ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY AND ALL |
| SPACES CONVERTED TO HABITABLE OR OCCUPIABLE SPACE IN |
| ANY WORK AREA SHALL BE PROVIDED WITH NATURAL OR |
| MECHANICAL VENTILATION IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, MECHANICAL. |
| EXCEPTION: EXISTING MECHANICAL VENTILATION SYSTEMS |
| SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 809.2. |
| 809.2 ALTERED EXISTING SYSTEMS. |
| IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL |
| VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR |
| EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER |
| MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR |
| AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION |
| AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF |
| VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY |
| PROCEDURE OF ASHRAE 62. |
| PLEASE PROVIDE VENTILATION CALCULATIONS IN COMPLIANCE |
| WITH TABLE 403.3 FBC-14 MECHANICAL. THE CALCULATIONS |
| SHALL INDICATE THE AMOUNT OF OUTSIDE AIR CFM'S |
| REQUIRED, AND THE AMOUNT OF OUTSIDE AIR CFM'S BEING |
| PROVIDED EITHER BY THE EXISTING OR MODIFIED HVAC |
| SYSTEMS. |
| 3) PLEASE PROVIDE MECHANICAL PLANS INDICATING ALL |
| PROPOSED ALTERATIONS TO THE EXISTING HVAC SYSTEMS. |
| |