2015-11-02 18:20:48 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND |
| BELOW ARE THE DEFICIENCIES NOTED. |
| THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN |
| ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING |
| CORRECTION: |
| |
| THERE WERE THE SAME PLANS PREVIOUSLY REVIEWED AND |
| SUBSEQUENTLY DENIED FOR LACK OF ELECTRICAL DATA. YOU |
| WERE PREVIOUSLY INSTRUCTED TO PROVIDE AN ELECTRICAL |
| SHEET WITH THE REQUIRED ELECTRICAL INFORMATION. |
| |
| 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATE SIGN |
| OUTLET AT EVERY PEDESTRIAN ENTRY INTO EVERY COMMERCIAL |
| ESTABLISHMENT. YOU ARE MISSING THE MAIN ENTRANCE AND |
| MAYBE EVEN THE REAR DOOR AS IT APPEARS TO BE AN ENTRY |
| FOR THE PRIVATE PARTY ROOM. |
| 2. THE SUBMITTED POWER PLAN FAILS TO INCLUDE THE |
| OUTLETS AND ADDITIONAL LOADS IN THE REAR AND KITCHEN |
| AREAS. |
| 3. YOU SHALL SUBMIT A LIGHTING PLAN THAT COMPLIES WITH |
| THE ENERGY CONSERVATION REQUIREMENTS OF THE FBC-ENERGY |
| CONSERVATION CODE. YOU SHALL ADDRESS THE LIGHT DENSITY |
| CHART, MANDATORY SWITCHING REQUIREMENTS AND THE |
| EFFICIENCY OF THE LUMINAIRES. |
| 4. ALL RECESSED LUMINARIES SHALL BE IC RATED AND SEALED |
| TO PREVENT TRANSFER OF AIR FROM THE CONDITIONED AIR |
| SPACE TO THE NON-CONDITIONED AIR SPACE. |
| 5. YOU SHALL PROVIDE THE FEEDER DIAGRAM WITH LOAD CALCS |
| AND CONDUCTOR SIZING AS REQUIRED IN NEC 215.5. |
| 6. YOU SHALL PROVIDE, FOR EVERY PANEL A CIRCUIT |
| DIRECTORY AS REQUIRED BY NEC 408.4 FOR EVERY PANEL |
| WITHIN THE PREMISES. EACH SHALL BE LABELED WITH AN |
| ARC-FLASH HAZARD WARNING LABEL AS INDICATED IN NEC |
| 110.16. |
| 7. FROM THE FLOOR PLAN AS PROVIDE, I CAN?T ACTUALLY |
| DETERMINE WHAT IS A GLASS WINDOW AND WHAT IS NOT, |
| THEREFORE KEEP IN MIND THE NEC 210.62 REQUIRES THAT |
| THERE BE A SHOW WINDOW OUTLET FOR EVERY 12 LINEAR FEET |
| OF SHOW WINDOW OR MAJOR PORTION THEREOF. |
| 8. YOU SHALL PROVIDE A ROOF PLAN OR INDICATE WHERE THE |
| CONDENSING UNITS FOR ALL REFRIGERATION EQUIPMENT ARE |
| LOCATED. |
| |
| IF AT ALL POSSIBLE, TO EXPEDITE THE ELECTRICAL REVIEW |
| PROCESS, A LESS CLUTTERED ELECTRICAL SHEET DRAWN TO A |
| LARGER SCALE WILL BE GREATLY APPRECIATED. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| |