2015-11-02 18:20:48THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND
 BELOW ARE THE DEFICIENCIES NOTED.
 THOUGH THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 ADDRESSED, THE NEW PLANS HAVE A COUPLE OF ITEMS NEEDING
 CORRECTION:
  
 THERE WERE THE SAME PLANS PREVIOUSLY REVIEWED AND
 SUBSEQUENTLY DENIED FOR LACK OF ELECTRICAL DATA. YOU
 WERE PREVIOUSLY INSTRUCTED TO PROVIDE AN ELECTRICAL
 SHEET WITH THE REQUIRED ELECTRICAL INFORMATION.
  
 1. NEC 600.5 REQUIRES THAT THERE BE A DEDICATE SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY INTO EVERY COMMERCIAL
 ESTABLISHMENT. YOU ARE MISSING THE MAIN ENTRANCE AND
 MAYBE EVEN THE REAR DOOR AS IT APPEARS TO BE AN ENTRY
 FOR THE PRIVATE PARTY ROOM.
 2. THE SUBMITTED POWER PLAN FAILS TO INCLUDE THE
 OUTLETS AND ADDITIONAL LOADS IN THE REAR AND KITCHEN
 AREAS.
 3. YOU SHALL SUBMIT A LIGHTING PLAN THAT COMPLIES WITH
 THE ENERGY CONSERVATION REQUIREMENTS OF THE FBC-ENERGY
 CONSERVATION CODE. YOU SHALL ADDRESS THE LIGHT DENSITY
 CHART, MANDATORY SWITCHING REQUIREMENTS AND THE
 EFFICIENCY OF THE LUMINAIRES.
 4. ALL RECESSED LUMINARIES SHALL BE IC RATED AND SEALED
 TO PREVENT TRANSFER OF AIR FROM THE CONDITIONED AIR
 SPACE TO THE NON-CONDITIONED AIR SPACE.
 5. YOU SHALL PROVIDE THE FEEDER DIAGRAM WITH LOAD CALCS
 AND CONDUCTOR SIZING AS REQUIRED IN NEC 215.5.
 6. YOU SHALL PROVIDE, FOR EVERY PANEL A CIRCUIT
 DIRECTORY AS REQUIRED BY NEC 408.4 FOR EVERY PANEL
 WITHIN THE PREMISES. EACH SHALL BE LABELED WITH AN
 ARC-FLASH HAZARD WARNING LABEL AS INDICATED IN NEC
 110.16.
 7. FROM THE FLOOR PLAN AS PROVIDE, I CAN?T ACTUALLY
 DETERMINE WHAT IS A GLASS WINDOW AND WHAT IS NOT,
 THEREFORE KEEP IN MIND THE NEC 210.62 REQUIRES THAT
 THERE BE A SHOW WINDOW OUTLET FOR EVERY 12 LINEAR FEET
 OF SHOW WINDOW OR MAJOR PORTION THEREOF.
 8. YOU SHALL PROVIDE A ROOF PLAN OR INDICATE WHERE THE
 CONDENSING UNITS FOR ALL REFRIGERATION EQUIPMENT ARE
 LOCATED.
  
 IF AT ALL POSSIBLE, TO EXPEDITE THE ELECTRICAL REVIEW
 PROCESS, A LESS CLUTTERED ELECTRICAL SHEET DRAWN TO A
 LARGER SCALE WILL BE GREATLY APPRECIATED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  