2015-11-01 11:32:101ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 IT IS DIFFICULT TO ACERTAIN IF THE SUBMITTED PLAN HAS
 AN ORIGINAL SIGNATUR FRO THE ENGINEER OF RECORD
 CHRISTIAN LANGLEY PE#67382. IS THE EASY SEAL INSIGNIA A
 DIGALTAL SIGNATURE AUTHENTIFICATION METHOD? PLEASE
 CONFIRM THE SEAL COMPLIES WITH THE CRITERIA IN FAC 61G
 OR IF INTENDED TO BE DIGITAL, THEN FAC 61G1-16.005, IF
 SO, SUBMIT DIGITALLY.
  
 THE PLAN PROVIDES FOR CONNECTOR OPTIONS BASED UPON THE
 SUBSTRATE. PLEASE IDENTIFY THE SUBSTRATE AND SPECIFY A
 CONNECTOR OPTION.
  
 SEE ELECTRICAL COMMENTS.
 THERE IS A STATEMENT ON THE PLAN INDICATING THE DESIGN
 IS FOR STRUCTURAL INTEGRITY ONLY AND THAT THE
 ELECTRICAL DESIGN ON THE PLAN IS THE SOLE
 RESPONSIBILITY OF THE ELECTRICIAN. PLEASE PROVIDE AN
 ELECTRICAL DESIGN BY SOMEONE RESPONSIBLE. INDICATE AT A
 MINIMUM COMPLIANCE WITH THE FOLLOWING AS APPLICABLE:
 APPLICABLE ELECTRICAL CODE IN EFFECT,
 NEC . 600, LISTING. DISCONNECT
 FBC 505, AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR
 WHEN NOT REQUIRED.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER