2015-11-01 11:32:10 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | | IT IS DIFFICULT TO ACERTAIN IF THE SUBMITTED PLAN HAS | | AN ORIGINAL SIGNATUR FRO THE ENGINEER OF RECORD | | CHRISTIAN LANGLEY PE#67382. IS THE EASY SEAL INSIGNIA A | | DIGALTAL SIGNATURE AUTHENTIFICATION METHOD? PLEASE | | CONFIRM THE SEAL COMPLIES WITH THE CRITERIA IN FAC 61G | | OR IF INTENDED TO BE DIGITAL, THEN FAC 61G1-16.005, IF | | SO, SUBMIT DIGITALLY. | | | | THE PLAN PROVIDES FOR CONNECTOR OPTIONS BASED UPON THE | | SUBSTRATE. PLEASE IDENTIFY THE SUBSTRATE AND SPECIFY A | | CONNECTOR OPTION. | | | | SEE ELECTRICAL COMMENTS. | | THERE IS A STATEMENT ON THE PLAN INDICATING THE DESIGN | | IS FOR STRUCTURAL INTEGRITY ONLY AND THAT THE | | ELECTRICAL DESIGN ON THE PLAN IS THE SOLE | | RESPONSIBILITY OF THE ELECTRICIAN. PLEASE PROVIDE AN | | ELECTRICAL DESIGN BY SOMEONE RESPONSIBLE. INDICATE AT A | | MINIMUM COMPLIANCE WITH THE FOLLOWING AS APPLICABLE: | | APPLICABLE ELECTRICAL CODE IN EFFECT, | | NEC . 600, LISTING. DISCONNECT | | FBC 505, AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR | | WHEN NOT REQUIRED. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|