Plan Review Notes
Plan Review Notes For Permit 15091328
Permit Number 15091328
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-01 12:59:16ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4
  
  