Date |
Text |
2015-12-09 10:18:21 | 2ND REVIEW: FBC 2014 5TH ED. |
| |
| PROVISIONALLY APPROVED: |
| |
| THE PURPOSE OF THIS APPLICATION IS TO ATTEMPT TO |
| LEGALLY ESTABLISH AN ATTACHED STORAGE ROOM THAT WAS |
| BUILT WITHOUT A PERMIT HOWEVER; THE APPLICATION |
| DESCRIPTION ONLY INDICATES POURING A SLAB AND IS VALUED |
| AT $500.00. THE PERMIT DESCRIPTION HAS BEEN CHANGED TO |
| AN APPROPRIATE DESCRIPTION AND THE VALUE IS INCREASED |
| TO $6,020.00 BASED FBC 109.3 RESULTING IN AN INCREASED |
| PERMIT FEE. |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| THE DOOR SUBMITTALS. |
| |
| PLEASE NOTE THE ROOFING PRODUCT SUPPLIED, NOA |
| 12-0601.10 REQUIRES ENHANCED FASTENING CALCULATIONS PER |
| IT'S LIMITATION #7. PLEASE PROVIDE AS A SUBMITTAL. |
| |
| PLEASE NOTE THE WINDOW PRODUCT APPROVAL ORIGINALLY |
| SUPPLIED WITH PERMIT 15070876 HAS BEEN INCORPORATED |
| INTO THIS APPLICATION AND APPLICATION 15070876 HAS BEEN |
| REVOKED AND FEES PAID IN ASSOCIATION WITH THAT |
| APPLICATION ARE TO BE CREDITED TO THIS APPLICATION. |
| |
| FBC 107.3.5.3 INDICATE THE MEANS OF TERMITE PROTECTION |
| PROPOSED PURSUANT TO FBC-R318. |
| |
| GENERAL AFTER THE FACT PERMITS |
| |
| FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A |
| PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| PURPOSES UNTIL APPROVED. |
| |
| FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |
| (561) 805-6710 |
| [email protected] |
| |