2015-11-17 07:49:07BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15091271
 ADD: 2600 N. FLAGLER DR. SUITE # 307
 CONT: RHODES REMODELING
 TEL: (561)798-1382
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV.17/ 2015
 ACTION: DENIED
  
 1) COMPLIED. CONTRACTOR (QUALIFIER) ACTING AS THE
 DESIGNER OF RECORD SHALL PRINT THEIR NAME, SIGN THEIR
 NAME AND LICENSE NUMBER TO THE PLANS THEY HAVE CREATED.
 107.1.
  
 2) THE FLOOR PLAN AND ITEMIZED LIST OF THE SCOPE OF
 WORK TO BE COMPLETED UNDER THIS PERMIT LIST THE REMOVAL
 OF FLOOR TILE IN THE MASTER BATH AND GUEST BATH. PLEASE
 PROVIDE COMPLIANCE WITH:
  
 2A)2ND REQUEST. THE REPORT SUBMITTED PROLEX MSC MEGA
 SOUND CONTROL MEMBRANE UNDERLAYMENT WITH A IIC = 68.0
 DB IS FO A 8 INCH SLAB WITH A DROPPED SUSPENDED PLENUM
 CEILING WITH INSULATION. THE REPORT HAS TO BE TESTED ON
 A 6 INCH CONCRETE SLAB NO DROPPED CEILING.
  
 1ST REVIEW. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) THE REPORT SUBMITTED PROLEX MSC MEGA SOUND CONTROL
 MEMBRANE UNDERLAYMENT WITH A STC = 72 DB IS FO A 8 INCH
 SLAB WITH A DROPPED SUSPENDED PLENUM CEILING WITH
 INSULATION. THE REPORT HAS TO BE TESTED ON A 6 INCH
 CONCRETE SLAB NO DROPPED CEILING.
  
  
 1ST REVIEW. FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C)COMPLIED. FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) 2ND REQUEST. MR BOARD CAN NOT BE USED IN A SHOWER.
 IT IS OK TO USE AROUND A TOLIET COMPARTMENT. SEE CODE
 SECTION BELOW.
  
 1ST REVIEW. THE FLOOR PLAN AND ITEMIZED LIST OF THE
 SCOPE OF WORK TO BE COMPLETED UNDER THIS PERMIT LIST
 THE REMOVAL OF SHOWER WALLS UP TO 48 INCHES. PLEASE
 PROVIDE WHAT TYPE OF TILE BACKING MATERIAL TO BE
 INSTALLED IN THE SHOWER.
 2014 FBC-B 2509.2 BASE FOR TILE.
 GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS,
 DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE
 SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS
 BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR
 C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER
 RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE
 IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN
 SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS.
 REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR
 WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER