2015-10-08 13:54:521ST REVIEW: FBC 2014 MECHANICAL
  
 1) REFER TO SECTION 601.2: AIR MOVEMENT IN EGRESS
 ELEMENTS.
 CORRIDORS SHALL NOT SERVE AS SUPPLY, RETURN, EXHAUST,
 RELIEF OR VENTILATION AIR DUCTS.
 PLEASE REVISE THE LAYOUT PLAN TO SHOW COMPLIANCE.
 2) DUCT SMOKE DETECTORS ARE SHOWN IN THE RETURN AIR
 PLENUMS: REFER TO SECTION 606.4 CONTROLS OPERATION, AND
 606.4.1 SUOERVISION, AND PROVIDE DETAILS INDICATING
 COMPLIANCE. PLEASE CLARIFY IF BOTH SYSTEMS WILL SHUT
 DOWN SIMULTANEOUSLY IF ONLY ONE SYSTEM DETECTOR
 ACTIVATES.
 3) PROVIDE WIND LOAD ENGINEERED TIE-DOWN DETAILS FOR
 ANCHORING THE AC CONDENSERS- SECTION 301.15 FBC-14
 MECHANICAL.
  