2015-11-03 16:40:06 | 2014 FBC ENERGY CONSERVATION R403.2.4 |
| AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE |
| FOLLOWING CONDITIONS ARE MET: |
| 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| 6 FEET (1829 MM) OF AN ATTIC ACCESS. |
| 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE |
| UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING |
| PROPERLY. |
| 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| REPLACE THE AIR HANDLER. |
| 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST |
| PARAGRAPH IN BOLD: |
| |
| NOTICE TO HOMEOWNER |
| |
| A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR |
| HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT |
| AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM, |
| YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. |
| YOUR AIR CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR |
| BOTH OF THE FOLLOWING: |
| |
| 1)A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION |
| DRAIN IS NOT WORKING PROPERLY OR |
| |
| 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE |
| CONDENSATION DRAIN IS NOT WORKING. |
| |
| TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID |
| DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU |
| ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE |
| EACH SEASON OF PEAK OPERATION. |
| |