Plan Review Notes
Plan Review Notes For Permit 15091242
Permit Number 15091242
Review Stop E
Sequence Number 1
Notes
Date Text
2015-11-03 13:11:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014) / NEC 2011
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 2) THE PLANS SHOW A MAIN LUG ONLY (MLO) PANEL RATHER
 THAN A MAIN CIRCUIT BREAKER (MCB) PANEL. SPECIFY THE
 LOCATION OF THE ELECTRIC METER AND SHOW THAT THE
 DISCONNECTING MEANS COMPLIES WITH NEC 225.31 & 225.32.
  
 3) THE FIRST FLOOR ELECTRICAL PLAN ONLY SHOW ONE A/C
 CONDENSING UNIT WITH A DISCONNECT AND THE MECHANICAL
 PLANS HAVE TWO CONDENSING UNITS. FBC 107.2.1
  
 4) AT LEAST ONE WEATHER PROOF GFCI RECEPTACLE OUTLET IS
 REQUIRED ON EACH BALCONY. NEC 210.52 (E) (3)
  
 5) THE AHU HEAT STRIPS ARE SPECIFIED AS 10KW IN THE
 PANEL SCHEDULE AND THE DEMAND IS LISTED AS 5 KVA. THE
 MECHANICAL PLANS SPECIFY 5 KW HEAT STRIPS. PLEASE
 COORDINATE. FBC107.2.1
  
 6) SMOKE ALARMS AND CARBON MONOXIDE DETECTORS ARE
 REQUIRED AT THE FIRST FLOOR FAMILY ROOM WHICH HAS A
 CLOSET AND COULD BE USED AS A SLEEPING ROOM. FBC-R314 &
 R315.
  
  
  
  
  