Plan Review Notes For Permit 15091242 |
Permit Number |
15091242 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-11-03 13:11:01 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) / NEC 2011 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. | | | | 2) THE PLANS SHOW A MAIN LUG ONLY (MLO) PANEL RATHER | | THAN A MAIN CIRCUIT BREAKER (MCB) PANEL. SPECIFY THE | | LOCATION OF THE ELECTRIC METER AND SHOW THAT THE | | DISCONNECTING MEANS COMPLIES WITH NEC 225.31 & 225.32. | | | | 3) THE FIRST FLOOR ELECTRICAL PLAN ONLY SHOW ONE A/C | | CONDENSING UNIT WITH A DISCONNECT AND THE MECHANICAL | | PLANS HAVE TWO CONDENSING UNITS. FBC 107.2.1 | | | | 4) AT LEAST ONE WEATHER PROOF GFCI RECEPTACLE OUTLET IS | | REQUIRED ON EACH BALCONY. NEC 210.52 (E) (3) | | | | 5) THE AHU HEAT STRIPS ARE SPECIFIED AS 10KW IN THE | | PANEL SCHEDULE AND THE DEMAND IS LISTED AS 5 KVA. THE | | MECHANICAL PLANS SPECIFY 5 KW HEAT STRIPS. PLEASE | | COORDINATE. FBC107.2.1 | | | | 6) SMOKE ALARMS AND CARBON MONOXIDE DETECTORS ARE | | REQUIRED AT THE FIRST FLOOR FAMILY ROOM WHICH HAS A | | CLOSET AND COULD BE USED AS A SLEEPING ROOM. FBC-R314 & | | R315. | | | | | | | | | | |
|