Plan Review Notes For Permit 15090899 |
Permit Number |
15090899 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-23 12:48:42 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. WPB AMEND. 107.2.1.4 QUALITY OF BUILDING PLANS. | | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | MEDIUM. THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS | | FOR PLANS AND SPECIFICATIONS, IN | | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION | | PROGRAM. THIS POLICY MAY INCLUDE SUCH | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | OTHER ITEMS RELATED TO RECORDS | | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH | | THE ARCHIVE REQUIREMENTS OF | | FLORIDA STATUTES. | | | | 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | 3. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | 4. TYPE OF GAS, (LP OR NATURAL). | | | | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 6. PLEASE CLARIFY WHICH IS EXISTING AMD WHICH IS NEW |
|