2015-10-22 08:57:31THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
 1. NO ELECTRICAL DATA PROVIDED.
 2. YOU SHALL SUBMIT AN ELECTRICAL WIRING DIAGRAM
 REFLECTING THE PROPOSED INSTALLATION, TAKING INTO
 CONSIDERATION ALL APPLICABLE MOTOR LOADS, VOLTAGE DROP
 AND DIRECT SUNLIGHT EXPOSURE OF YOUR CONDUCTORS.
 3. YOU SHALL SUBMIT SPEC SHEETS ON THE PROPOSED LIFT
 INCLUDING MOTOR LOADS.
 4. YOU SHALL INCLUDE THE LOCATION OF THE SERVICE, MAIN
 DISCONNECT AND ALL ASSOCIATED EQUIPMENT. ALL THIS SHALL
 BE LOCATED TAKING INTO CONSIDERATION ALL THE
 REQUIREMENTS OF NEC 682. (BE AWARE OF THE ELECTRICAL
 DATUM PLANE WHEN LOCATING THE EQUIPMENT)
 5. IN ADDITION TO THE ELECTRIC FOR THE HOIST MOTORS,
 AND 15-20 AMP 120 V. GFCI PROTECTED OUTLET SHALL BE
 PROVIDED FOR SERVICE AND SHORE POWER.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  