2015-10-22 08:57:31 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| OF THE FBC, (FLORIDA BUILDING CODE) 2014, AS APPLICABLE |
| AND BELOW ARE THE DEFICIENCIES NOTED. |
| 1. NO ELECTRICAL DATA PROVIDED. |
| 2. YOU SHALL SUBMIT AN ELECTRICAL WIRING DIAGRAM |
| REFLECTING THE PROPOSED INSTALLATION, TAKING INTO |
| CONSIDERATION ALL APPLICABLE MOTOR LOADS, VOLTAGE DROP |
| AND DIRECT SUNLIGHT EXPOSURE OF YOUR CONDUCTORS. |
| 3. YOU SHALL SUBMIT SPEC SHEETS ON THE PROPOSED LIFT |
| INCLUDING MOTOR LOADS. |
| 4. YOU SHALL INCLUDE THE LOCATION OF THE SERVICE, MAIN |
| DISCONNECT AND ALL ASSOCIATED EQUIPMENT. ALL THIS SHALL |
| BE LOCATED TAKING INTO CONSIDERATION ALL THE |
| REQUIREMENTS OF NEC 682. (BE AWARE OF THE ELECTRICAL |
| DATUM PLANE WHEN LOCATING THE EQUIPMENT) |
| 5. IN ADDITION TO THE ELECTRIC FOR THE HOIST MOTORS, |
| AND 15-20 AMP 120 V. GFCI PROTECTED OUTLET SHALL BE |
| PROVIDED FOR SERVICE AND SHORE POWER. |
| THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN |
| MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED |
| FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED |
| TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| APPRECIATED. |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| |