2015-11-21 07:49:57 | 1) SUBMIT INTERCEPTOR SIZING CALCULATIONS. THE | | INTERCEPTOR SHALL BE SIZED IN ACCORDANCE WITH ONE OF | | THE METHODS LISTED IN THE 2010 FBC SEC.1003.3.4. 2ND | | REQUEST. | | 2) SUBMIT MANUF. SPECS FOR THE ADDED GAS EQUIPMENT AND | | SUBMIT A COMPLETE GAS DRAWING FOR REVIEW.WPB AMEND. TO | | FBC SEC. 107.2.1. 2ND REQUEST | | 3) SHT.P-4 - SHOWS THE DRAINS FROM ICE BINS DISCHARGING | | INTO THE GREASE INTERCEPTOR.WASTES THAT DO NOT REQUIRE | | TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO | | ANY INTERCEPTOR OR SEPARATOR PER 2010 FBC-PLUMBING | | SEC.1003.2. 2ND REQUEST. | | 4) GREASE INTTERCEPTORS SHALL BE EQUIPPED WITH DEVICES | | TO CONTROL THE RATE OF WATER FLOW SO THAT THE WATER | | FLOW DOES NOT EXCEED THE RATED FLOW PER FBC-PLUMBING | | SEC.1003.3.4.2. 2ND REQUEST. REFER TO THE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS THAT I PRINTED | | OUT SINCE THEY WERE NOT SUBMITTED AS PREVIOUSLY | | REQUESTED.SHOW THE REQUIRED VENT ON THE RISER | | DIAGRAM.THE VENT FOR THE SERVICE SINK WILL NOT SUFFICE | | FOR THE INTERCEPTOR. | | 5) SUBMIT A WATER RISER FOR REVIEW FOR THE CHANGES MADE | | TO THE WATER PIPING SYSTEM. WPB AMEND. TO FBC SEC. | | 107.3.5.1.3.2ND REQUEST. | | 6) SUBMIT AN EXPANDED SANITARY RISER DIAGRAM. IT IS | | DIFFICULT TO SEE WHERE ONE LINE STOPS AND ANOTHER | | BEGINS. WPB AMEND. TO FBC SEC. 107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|