Plan Review Notes
Plan Review Notes For Permit 15090732
Permit Number 15090732
Review Stop P
Sequence Number 2
Notes
Date Text
2015-11-21 07:49:571) SUBMIT INTERCEPTOR SIZING CALCULATIONS. THE
 INTERCEPTOR SHALL BE SIZED IN ACCORDANCE WITH ONE OF
 THE METHODS LISTED IN THE 2010 FBC SEC.1003.3.4. 2ND
 REQUEST.
 2) SUBMIT MANUF. SPECS FOR THE ADDED GAS EQUIPMENT AND
 SUBMIT A COMPLETE GAS DRAWING FOR REVIEW.WPB AMEND. TO
 FBC SEC. 107.2.1. 2ND REQUEST
 3) SHT.P-4 - SHOWS THE DRAINS FROM ICE BINS DISCHARGING
 INTO THE GREASE INTERCEPTOR.WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANY INTERCEPTOR OR SEPARATOR PER 2010 FBC-PLUMBING
 SEC.1003.2. 2ND REQUEST.
 4) GREASE INTTERCEPTORS SHALL BE EQUIPPED WITH DEVICES
 TO CONTROL THE RATE OF WATER FLOW SO THAT THE WATER
 FLOW DOES NOT EXCEED THE RATED FLOW PER FBC-PLUMBING
 SEC.1003.3.4.2. 2ND REQUEST. REFER TO THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS THAT I PRINTED
 OUT SINCE THEY WERE NOT SUBMITTED AS PREVIOUSLY
 REQUESTED.SHOW THE REQUIRED VENT ON THE RISER
 DIAGRAM.THE VENT FOR THE SERVICE SINK WILL NOT SUFFICE
 FOR THE INTERCEPTOR.
 5) SUBMIT A WATER RISER FOR REVIEW FOR THE CHANGES MADE
 TO THE WATER PIPING SYSTEM. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.2ND REQUEST.
 6) SUBMIT AN EXPANDED SANITARY RISER DIAGRAM. IT IS
 DIFFICULT TO SEE WHERE ONE LINE STOPS AND ANOTHER
 BEGINS. WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  