Plan Review Notes For Permit 15090732 |
Permit Number |
15090732 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-02-05 17:21:42 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15090732 | | 2/5/16 | | | | 1) THE HEAT LOAD SUMMARY ON SHEET M-1 IS INCOMPLETE AND | | SHALL BE SUBMITTED ON A SEPARATE SIGNED AND SEALED | | SUMMARY SHEET- REFER TO SECTION 503.2.1 FBC-10 ENERGY | | CONSERVATION (EXCEPTION): | | WHERE MECHANICAL SYSTEMS ARE DESIGNED BY A REGISTERED | | ENGINEER, THE ENGINEER HAS THE OPTION OF SUBMITTING A | | SIGNED AND SEALED SUMMARY SHEET TO THE BUILDING | | DEPARTMENT IN LIEU OF THE COMPLETE SIZING | | CALCULATION(S). SUCH SUMMARY SHEET SHALL INCLUDE THE | | FOLLOWING (BY ZONE): | | 1. PROJECT NAME/OWNER | | 2. PROJECT ADDRESS | | 3. AREA IN SQUARE FEET | | 4. SIZING METHOD USED | | 5. OUTDOOR DRY BULB USE | | 6. INDOOR DRY BULB | | 7. OUTDOOR WET BULB USED | | 8. GRAINS WATER (DIFFERENCE) | | 9. TOTAL SENSIBLE GAIN | | 10. TOTAL LATENT GAIN | | 11. RELATIVE HUMIDITY | | 12. TOTAL COOLING REQUIRED WITH OUTSIDE AIR | | 13. TOTAL HEATING REQUIRED WITH OUTSIDE AIR | | 2) UNDER THIS REVISION, PLEASE CLARIFY HOW THE THE HEAT | | LOAD HAS INCREASED FROM 131 MBH TO 230 MBH COOLING , | | AND 35.8 TO 83 MBH HEATING WHEN THERE APPEARS TO BE NO | | APPARENT CHANGE IN THE ZONE, THE OCCUPANT LOAD, OR THE | | OUTSIDE AIR INTAKE. | | 3) DUE TO THE CHANGE IN THE 1ST FLOOR AC SYSTEM, A | | REVISED ENERGY CALCULATION FORM 506-2010 MUST BE | | SUBMITTED. | | 4) PROVIDE AN AIR BALANCE CALCULATION ON THE PLAN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|