Plan Review Notes
Plan Review Notes For Permit 15090732
Permit Number 15090732
Review Stop E
Sequence Number 2
Notes
Date Text
2016-02-24 14:22:582ND ELECTRICAL REVIEW NOTES FOR REVISION #:15090732
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2010 EDITION
 NFPA 70 2008 (NEC)
  
 CORRECTIONS REQUIRED:
 IN FOLLOWING YOUR RESPONSE LETTER ON THE ELECTRICAL
 REVIEW COMMENTS OF THE PREVIOUS REVIEW, BELOW IS A LIST
 OF ITEMS THAT REQUIRE FURTHER EXPLANATION OR ACTION.
 THESE WILL BE NUMBERED AS IN THE INITIAL REVIEW BECAUSE
 THEY ARE NOT NEW COMMENTS BUT PREVIOUS COMMENTS NOT
 PROPERLY ADDRESSED.
 1. COMMENT #3 DEALING WITH THE SHOW WINDOW OUTLETS. NEC
 210.62 REQUIRES THAT THERE BE AN OUTLET WITHIN 18" OF
 THE TOP OF THE WINDOW FOR EVERY 12' OF WINDOW OR MAJOR
 PORTION THEREOF. IT DOESN'T MEAN THAT IF YOU HAVE TWO
 6' WINDOWS A SINGLE OUTLET WILL DO. YOU SHALL HAVE AN
 OUTLET WITHIN 18" OF THE TOP OF EACH WINDOW.
 2. COMMENT #6 DEALING WITH THE "WEATHER RESISTANT"
 RECEPTACLES. NEC 406.8(B) REQUIRES THAT ALL RECEPTACLES
 IN WET LOCATIONS BE IN ADDITION TO THE WEATHER-PROOF
 ENCLOSURE, ALSO BE LISTED AS WEATHER-RESISTANT "WR".
 3. COMMENT #7 DEALS WITH THE DEDICATED SIGN OUTLET. NEC
 600.5 REQUIRES THAT THERE BE IN AN ACCESSIBLE LOCATION
 A DEDICATED OUTLET FOR SIGNAGE AT EVERY PEDESTRIAN
 ENTRY DOOR.
 4. COMMENT #8 EMERGENCY AND EXIT LIGHTS. THE EMERGENCY
 LIGHTING AS SHOWN ON THE PLANS DOES NOT MEET MINIMUM
 STANDARDS. IN ADDITION TO EMERGENCY LIGHTING, AN EXIT
 LIGHT IS MISSING TO INDICATE THE REAR EXIT CORRIDOR AS
 THAT SIGN ABOVE THE DOOR IS NOT VISIBLE FROM LOCATIONS
 WITHIN THE PREMISES.
 5. COMMENT #9 CONTINUES TO DEAL WITH THE EMERGENCY AND
 EXIT LIGHTS. NEC 700.12 REQUIRES THAT EMERGENCY LIGHTS
 BE ON THE SAME CIRCUIT AS THE LIGHTING OF THE AREA
 WHICH THEY OCCUPY. WHETHER AHEAD OF THE SWITCH OR NOT
 DOES NOT INDICATE COMPLIANCE WITH CODE. MARK ON THE
 PLANS THE LIGHTING CIRCUIT USED TO POWER THE EMERGENCY
 LIGHTS WHEN THEY ARE INCORPORATED INTO THE PLANS.
 6. COMMENT #10 ASKS FOR DEFINITION OF THE FEEDER
 CONDUCTORS OF THE RISER DIAGRAM. ACCORDING TO YOUR LOAD
 CALCS FOR PANEL B, THE CONNECTED LOAD IS 152 AMP. PER
 NEC 310.15 THE AMPACITY OF THE #2 CONDUCTOR IS ONLY 115
 AMP. THE SAME APPLIES TO THE CONDUCTORS FOR PANEL A.
 CONNECTED LOAD OF 291 AMP FEED WITH A 3/0 CONDUCTOR
 LISTED FOR ONLY 200 AMP. THIS IS ALL ASSUMING THAT YOU
 ARE USING COPPER CONDUCTORS WITH 75 DEGREE INSULATION
 WHICH AGAIN IS NOT DEFINED. PER NEC 220.88, THE
 CONNECTED LOADS OF BOTH PANELS (160 KW) BEING <200 KW
 FOR A NOT ALL ELECTRIC RESTAURANT BE CONSIDERED AT 100
 DEMAND. THEREFORE 160 KW @ 208 V. 3? HAS A CONNECTED
 LOAD VALUE OF 443 AMP. MAIN FEEDER CONDUCTORS SHALL BE
 SIZED ACCORDINGLY.
 7. COMMENT #11 ENERGY CODE REQUIREMENTS. IN ADDITION TO
 THE LIGHTING POWER DENSITY ALLOWANCES THE FBC-ENERGY
 CONSERVATION SECTION HAS MANDATORY SWITCHING & LIGHTING
 CONTROL REQUIREMENTS WHICH SHALL BE ADDRESSED ON THE
 PLANS.
 8. COMMENT #12 FIXTURE SCHEDULE. INCLUDE IN THE FIXTURE
 SCHEDULE THE TYPE AND LABEL DESIGNATOR FOR THE PROPOSED
 EMERGENCY LIGHTING FIXTURE AND/OR NIGHT LIGHT FIXTURE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  