2016-02-24 14:22:58 | 2ND ELECTRICAL REVIEW NOTES FOR REVISION #:15090732 |
| REVIEWED FOR COMPLIANCE WITH: |
| FBC 2010 EDITION |
| NFPA 70 2008 (NEC) |
| |
| CORRECTIONS REQUIRED: |
| IN FOLLOWING YOUR RESPONSE LETTER ON THE ELECTRICAL |
| REVIEW COMMENTS OF THE PREVIOUS REVIEW, BELOW IS A LIST |
| OF ITEMS THAT REQUIRE FURTHER EXPLANATION OR ACTION. |
| THESE WILL BE NUMBERED AS IN THE INITIAL REVIEW BECAUSE |
| THEY ARE NOT NEW COMMENTS BUT PREVIOUS COMMENTS NOT |
| PROPERLY ADDRESSED. |
| 1. COMMENT #3 DEALING WITH THE SHOW WINDOW OUTLETS. NEC |
| 210.62 REQUIRES THAT THERE BE AN OUTLET WITHIN 18" OF |
| THE TOP OF THE WINDOW FOR EVERY 12' OF WINDOW OR MAJOR |
| PORTION THEREOF. IT DOESN'T MEAN THAT IF YOU HAVE TWO |
| 6' WINDOWS A SINGLE OUTLET WILL DO. YOU SHALL HAVE AN |
| OUTLET WITHIN 18" OF THE TOP OF EACH WINDOW. |
| 2. COMMENT #6 DEALING WITH THE "WEATHER RESISTANT" |
| RECEPTACLES. NEC 406.8(B) REQUIRES THAT ALL RECEPTACLES |
| IN WET LOCATIONS BE IN ADDITION TO THE WEATHER-PROOF |
| ENCLOSURE, ALSO BE LISTED AS WEATHER-RESISTANT "WR". |
| 3. COMMENT #7 DEALS WITH THE DEDICATED SIGN OUTLET. NEC |
| 600.5 REQUIRES THAT THERE BE IN AN ACCESSIBLE LOCATION |
| A DEDICATED OUTLET FOR SIGNAGE AT EVERY PEDESTRIAN |
| ENTRY DOOR. |
| 4. COMMENT #8 EMERGENCY AND EXIT LIGHTS. THE EMERGENCY |
| LIGHTING AS SHOWN ON THE PLANS DOES NOT MEET MINIMUM |
| STANDARDS. IN ADDITION TO EMERGENCY LIGHTING, AN EXIT |
| LIGHT IS MISSING TO INDICATE THE REAR EXIT CORRIDOR AS |
| THAT SIGN ABOVE THE DOOR IS NOT VISIBLE FROM LOCATIONS |
| WITHIN THE PREMISES. |
| 5. COMMENT #9 CONTINUES TO DEAL WITH THE EMERGENCY AND |
| EXIT LIGHTS. NEC 700.12 REQUIRES THAT EMERGENCY LIGHTS |
| BE ON THE SAME CIRCUIT AS THE LIGHTING OF THE AREA |
| WHICH THEY OCCUPY. WHETHER AHEAD OF THE SWITCH OR NOT |
| DOES NOT INDICATE COMPLIANCE WITH CODE. MARK ON THE |
| PLANS THE LIGHTING CIRCUIT USED TO POWER THE EMERGENCY |
| LIGHTS WHEN THEY ARE INCORPORATED INTO THE PLANS. |
| 6. COMMENT #10 ASKS FOR DEFINITION OF THE FEEDER |
| CONDUCTORS OF THE RISER DIAGRAM. ACCORDING TO YOUR LOAD |
| CALCS FOR PANEL B, THE CONNECTED LOAD IS 152 AMP. PER |
| NEC 310.15 THE AMPACITY OF THE #2 CONDUCTOR IS ONLY 115 |
| AMP. THE SAME APPLIES TO THE CONDUCTORS FOR PANEL A. |
| CONNECTED LOAD OF 291 AMP FEED WITH A 3/0 CONDUCTOR |
| LISTED FOR ONLY 200 AMP. THIS IS ALL ASSUMING THAT YOU |
| ARE USING COPPER CONDUCTORS WITH 75 DEGREE INSULATION |
| WHICH AGAIN IS NOT DEFINED. PER NEC 220.88, THE |
| CONNECTED LOADS OF BOTH PANELS (160 KW) BEING <200 KW |
| FOR A NOT ALL ELECTRIC RESTAURANT BE CONSIDERED AT 100 |
| DEMAND. THEREFORE 160 KW @ 208 V. 3? HAS A CONNECTED |
| LOAD VALUE OF 443 AMP. MAIN FEEDER CONDUCTORS SHALL BE |
| SIZED ACCORDINGLY. |
| 7. COMMENT #11 ENERGY CODE REQUIREMENTS. IN ADDITION TO |
| THE LIGHTING POWER DENSITY ALLOWANCES THE FBC-ENERGY |
| CONSERVATION SECTION HAS MANDATORY SWITCHING & LIGHTING |
| CONTROL REQUIREMENTS WHICH SHALL BE ADDRESSED ON THE |
| PLANS. |
| 8. COMMENT #12 FIXTURE SCHEDULE. INCLUDE IN THE FIXTURE |
| SCHEDULE THE TYPE AND LABEL DESIGNATOR FOR THE PROPOSED |
| EMERGENCY LIGHTING FIXTURE AND/OR NIGHT LIGHT FIXTURE. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |