Plan Review Notes
Plan Review Notes For Permit 15090732
Permit Number 15090732
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-18 08:48:071) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALL MANUAL
 FOR THE ZURN GREASE INTERCEPTOR FOR REVIEW. WPB AMEND.
 TO FBC SEC.107.2.1, 107.3.5.1.3.
 2) SUBMIT INTERCEPTOR SIZING CALCULATIONS. THE
 INTERCEPTOR SHALL BE SIZED IN ACCORDANCE WITH ONE OF
 THE METHODS LISTED IN THE 2010 FBC SEC.1003.3.4.
 3) SUBMIT A REVISED KITCHEN EQUIPMENT SCHEDULE. THE
 PLANS SHOW A NEW GRIDDLE AND FRYER BUT NO INFORMATION
 HAS BEEN SUBMITTED FOR THESE APPLIANCES.
 4) INDICATE ON THE PLANS IF THE GRIDDLE AND FRYER ARE
 GAS OR ELECTRIC. IF THE APPLIANCES ARE GAS, THEN SUBMIT
 MANUF. SPECS FOR THE EQUIPMENT AND SUBMIT A COMPLETE
 GAS DRAWING FOR REVIEW. IF THE APPLIANCES ARE ELECTRIC,
 SUBMIT COMPLETE ELECTRIC PLANS FOR REVIEW.WPB AMEND. TO
 FBC SEC. 107.2.1.
 5) THE PLANS FOR THIS PLUMBING REVISION SHOW CHANGES
 FRROM THE ORIGINAL PLANS THAT APPEAR TO AFFECT
 STRUCTURAL, MECHANICAL AND ELECTRICAL DISCIPLINES.
 SUBMIT A COMPLETE SET OF PLANS THAT REFLECTS THE ENTIRE
 SCOPE OF CHANGES THAT HAVE BEEN MADE FROM THE ORIGINAL
 PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT.P-4 - SHOWS THE DRAINS FROM ICE BINS DISCHARGING
 INTO THE GREASE INTERCEPTOR.WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANY INTERCEPTOR OR SEPARATOR PER 2010 FBC-PLUMBING
 SEC.1003.2.
 7)THE GREASE INTERCEPTOR SHALL HAVE THE GREASE
 RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1 OF
 FBC-PLUMBING FOR THE FLOW THROUGH RATES INDICATED.
 8) GREASE INTTERCEPTORS SHALL BE EQUIPPED WITH DEVICES
 TO CONTROL THE RATE OF WATER FLOW SO THAT THE WATER
 FLOW DOES NOT EXCEED THE RATED FLOW PER FBC-PLUMBING
 SEC.1003.3.4.2.
 9) INDICATE THE TYPE OF COOKING OPERATIONS THAT WILL BE
 DONE IN THE STRUCTURE.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC
 SEC. 107.3.5.1.3.
  
 WHEN A COMPLETE SET OF PLANS ARE SUBMITTED THAT SHOW
 ALL THE CHANGES TO THE BUILDING, ELECTRICAL, MECHANICAL
 AND PLUMBING SYSTEMS THOSE PLANS WILL BE REVIEWED BY
 EACH DISCIPLINE. THE PLANS MUST BE SUBMITTED AS A
 COMPLETE PACKAGE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved