Notes |
Date |
Text |
2015-11-23 11:11:39 | 1ST REVIEW 2010 MECHANICAL | | REVISION #15090732 | | MASTER #14030818 | | 11/23/15 | | | | 1) REVISE THE HEAT LOAD AND AIR BALANCE CALCULATIONS TO | | INCLUDE THE NEW GAS-FIRED APPLIANCES AND EXHAUST HOOD | | IN THE NEW 1ST FLOOR KITCHEN. | | 2) PLACE A NOTE ON THE PLAN INDICATING THE KITCHEN | | HOOD, THE KITCHEN HOOD FIRE SUPPRESSION, AND THE | | WALK-IN BOXES WILL BE DONE UNDER SEPARATE PERMIT. | | 3) CLARIFY IF A SHAFT WILL BE CONSTRUCTED TO HOUSE THE | | NEW GREASE DUCT INSTALLATION, AND PROVIDE DETAILS ON | | THE PLAN IF APPLICABLE | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|