2015-12-30 13:53:44 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1. CLEARLY DEFINE YOUR SCOPE OF WORK ON BOTH, THE |
| REVISION FORM AND PLANS. THEY MUST MATCH. |
| 2. NEC 210.8 REQUIRES THAT ALL RECEPTACLES IN KITCHENS, |
| BATHROOMS AND ROOFTOPS BE GFCI PROTECTED. |
| 3. NEC 210.62. AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR |
| EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA |
| MEASURED HORIZONTALLY. BASED ON THE MEASURED SHOW |
| WINDOW FOOTAGE ON THE PLANS, YOU SHALL ADD AN |
| ADDITIONAL SHOW WINDOW OUTLET FOR BOTH THE DOWNSTAIRS |
| WINDOW AS WELL AS THE UPSTAIRS. |
| 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| 50 LB. ADD THIS TO THE NOTES ON CEILING OUTLETS. |
| 5. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| PADDLE FANS HEAVIER THAN 70 LBS. |
| 6. NEC 406.8(B), RECEPTACLES OUTDOORS OR EXPOSED TO THE |
| WEATHER SHALL BE LISTED WEATHER-RESISTANT ?WR?. |
| 7. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL |
| BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP |
| DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH |
| ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE |
| LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE |
| CONSIDERED ACCESSIBLE TO PEDESTRIANS. |
| 8. REVISE YOUR PLANS TO INCLUDE THE REQUIRED EMERGENCY |
| AND EXIT LIGHTING. |
| 9. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| OWN CIRCUIT. |
| 10. REDEFINE THE FEEDERS BETWEEN THE METER AND THE |
| FIRST DISCONNECT. INCLUDE CONDUCTOR INSULATION & |
| RACEWAY SIZING. |
| 11. FBC-E 505 HAS SPECIFIC MANDATORY ELECTRICAL POWER |
| AND LIGHTING SYSTEMS REQUIREMENTS WHICH SHALL BE |
| ADHERED TO. |
| 12. THE FIXTURE SCHEDULE AS SUBMITTED REFERS TO A NOTE |
| 3 NOT IDENTIFIED ON THE PLANS. |
| 13. PROVIDE A FIXTURE SCHEDULE AS REQUIRED ALONG WITH |
| THE REQUIRED LIGHT DENSITY CHART TO SHOW COMPLIANCE. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |