Plan Review Notes
Plan Review Notes For Permit 15090732
Permit Number 15090732
Review Stop E
Sequence Number 1
Notes
Date Text
2015-12-30 13:53:44THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. CLEARLY DEFINE YOUR SCOPE OF WORK ON BOTH, THE
 REVISION FORM AND PLANS. THEY MUST MATCH.
 2. NEC 210.8 REQUIRES THAT ALL RECEPTACLES IN KITCHENS,
 BATHROOMS AND ROOFTOPS BE GFCI PROTECTED.
 3. NEC 210.62. AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EVERY 12 LINEAR FT. OR MAJOR PORTION THEREOF AREA
 MEASURED HORIZONTALLY. BASED ON THE MEASURED SHOW
 WINDOW FOOTAGE ON THE PLANS, YOU SHALL ADD AN
 ADDITIONAL SHOW WINDOW OUTLET FOR BOTH THE DOWNSTAIRS
 WINDOW AS WELL AS THE UPSTAIRS.
 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING OUTLETS.
 5. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 6. NEC 406.8(B), RECEPTACLES OUTDOORS OR EXPOSED TO THE
 WEATHER SHALL BE LISTED WEATHER-RESISTANT ?WR?.
 7. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE
 CONSIDERED ACCESSIBLE TO PEDESTRIANS.
 8. REVISE YOUR PLANS TO INCLUDE THE REQUIRED EMERGENCY
 AND EXIT LIGHTING.
 9. NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 10. REDEFINE THE FEEDERS BETWEEN THE METER AND THE
 FIRST DISCONNECT. INCLUDE CONDUCTOR INSULATION &
 RACEWAY SIZING.
 11. FBC-E 505 HAS SPECIFIC MANDATORY ELECTRICAL POWER
 AND LIGHTING SYSTEMS REQUIREMENTS WHICH SHALL BE
 ADHERED TO.
 12. THE FIXTURE SCHEDULE AS SUBMITTED REFERS TO A NOTE
 3 NOT IDENTIFIED ON THE PLANS.
 13. PROVIDE A FIXTURE SCHEDULE AS REQUIRED ALONG WITH
 THE REQUIRED LIGHT DENSITY CHART TO SHOW COMPLIANCE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER