2015-09-24 19:04:37 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 2) A FLORIDA LICENSED DESIGN PROFESSIONAL IS REQURED TO |
| PREPARE THE PLANS. |
| FS 481.229 -EXCEPTIONS; EXEMPTIONS FROM LICENSURE. |
| (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN |
| ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS |
| FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR |
| ALTERATION OF: |
| (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY |
| FARMER, REGARDLESS OF THE COST OF THE BUILDING; |
| (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING, |
| TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY |
| ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST; |
| OR |
| (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN |
| $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING |
| INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF |
| A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR |
| SCHOOL PROJECTS PURSUANT TO S. 1013.45. |
| |
| 3) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS PER |
| EXISTING BUILDING CODE CHAPTER 5. |
| |
| 4) SUBMIT TEST REPORTS (AIR BORNE SOUND, STRUCTURE |
| BORNE SOUND, FLAME SPRED AND SMOKE DEVELOPED) FOR THE |
| REQUIRED FLOOR SOUND INSULATING UNDERLAYMENT. |
| FBC 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| FBC 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II |
| CONSTRUCTION |
| 603.1 ALLOWABLE MATERIALS. |
| COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| THROUGH 603.1.3: |
| 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM |
| PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN |
| 25. |
| EXCEPTIONS: |
| 1. INSULATION PLACED BETWEEN TWO LAYERS OF |
| NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 100. |
| 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 200. |
| 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26. |
| FBC 2603 FOAM PLASTIC INSULATION |
| 2603.3 SURFACE-BURNING CHARACTERISTICS. |
| UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM |
| PLASTIC INSULATION AND FOAM PLASTIC CORES OF |
| MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT |
| MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS |
| INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL |
| 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE |
| TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND |
| SMOKE-DEVELOPED INDEXES. |
| |
| 5) SPECIFY THE FRAMING MATERIAL THAT WILL BE USED TO |
| SHOW THAT IT WILL COMPLY WITH FBC 602.2. |
| TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF |
| CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN |
| TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS |
| PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE. |
| |
| |
| |
| |
| |
| |