2015-11-07 06:38:471)SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS
 APPLIANCES LOCATED ON THE INTERIOR OF THE STRUCTURE.
 COMPLY W/2010 FBC-RESIDENTIAL SEC.G2407.1 & G2407.5
 THROUGH G2407.11.
 2) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS. IT
 APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO
 FBC SEC. 107.1.
 3) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT SHOW
 THAT THE RANGE OR THE DRYER IS LISTED AND LABELED IN
 ACCORDANCE WITH 2010 FBC- SEC. G2404.3.
 4) SUBMIT MANUF. SPECIFICATIONS FOR THE OPTIONAL GRILL.
 WPB AMEND. TO FBC SEC. 107.1.
 5) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL
 BE ONSITE FOR THE INSPECTOR PER THE 2010 FBC-RES. SEC.
 G 2408.1.
 6) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN
 THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF
 PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF
 PENETRATION, ETC. COMPLY WITH 2010 FBC-RES.SECS.G2426 &
 G2427.
  